WALL-MOUNTED CONTROLS
ATW wall-mounted control
The ATW control is used to regulate the air (3 speeds + auto), the temperature through electronic thermostat, to select the sum-
mer/winter/auto mode of operation and to switch the fan coil on/off.
Technical data
Supply voltage
Supply frequency
Contact rating
Remote air sensor
Remote water sensor
Regulation range
Storage temperature
Max. storage humidity
Working temperature
Max. working humidity
Protection rating
Case material
Color
Dimensions
Weight
34
EN
Temperature selector
Adjust the temperature as
required by turning the
temperature selector from +14°C
to 30°C.
Function selector
Select the mode of operation
pushing the
buttom.
Cooling
Heating
Off
Automatic setting
Speed selector
Select the fan speed pushing the
The repeated pressure of fan button
determines speed required.
Maximum fan speed
Medium fan speed
Minimum fan speed
Automatic fan speed
Led
Blue LED: Heating / Cooling
plus regulator call
Blue LED blinking: Hot start / Too Cool
function active
Blue LED:
operation in Cooling mode
Blue LED:
operation in Heating mode
Blue LED:
automatic cooling / heating
mode selection
230 V ~ ±10%
50/60 Hz
1A (cosØ ≥0.85; 230V)
10 kOhm @ T = 25 °C
10 kOhm @ T = 25 °C
+14°C a 30°C
-20 °C / +85 °C
90% (not condensing)
0 °C / +55 °C
90% (not condensing)
IP 30
PC+ABS (flame retardant V0)
RAL 9003 (white)
120 x 75 x 25 mm
0,265 kg