Installation Instructions; Operating Instructions - Sola HD SDU Serie Manual De Instrucciones

Ocultar thumbs Ver también para SDU Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Placement: Install the UPS in a protected area with adequate airflow and free
of excessive dust. Do not operate the UPS outdoors.
2. Connect to Utility: To power up the UPS, connect the ac input connector to
the utility power.
3. Charge the Battery: The UPS charges its battery whenever it is connected to
utility power. For best results, charge the battery for four hours during initial use.
4. Connect the Loads: Connect the loads to the output hardwire connector.
5. Apply the Electrical Shock Warning Label: Apply the electrical shock
warning label to the panel, in a way that is clearly visible to the user.
6. Do not connect Ground to Neutral on either input or output terminals of the UPS
unit.
1. Output Connector: The output connector will provide protection from surges
and power failures to the critical loads.
2. Switch ON Green Mode Enabled: After connecting the UPS to the utility
power, press the ON button until you hear the first beep, then release the
button immediately. The Green Mode is enabled, i.e. if a load less than forty
watts (or no load) is connected and the UPS operates in the Backup Mode.
The UPS will enter into the Green Mode status after three minutes of backup
time; the green light will flash every three to five seconds and after a short
period of time; and the unit will enter a "power save" status by shutting down
to prevent deep discharge of the battery. To reactivate the unit, power the unit
OFF then ON again or reapply utility power.
3. Switch ON Green Mode Disabled: After connecting the UPS to the utility
power, press the ON button and keep pressing it until you hear two short
beeps "Bi-Bip", then release the button immediately. The Green Mode is now
disabled. Any kind of load, whether smaller than forty watts or larger, will not
affect the normal operation of the UPS under Ac or Battery Mode.
4. Switch OFF: To switch OFF the UPS, press and hold the Power ON/OFF/Test
button until the "Ac Power Normal" LED or "ON Battery" LED turns OFF.
English version

5.0 Installation Instructions

hazardous live parts inside this
panel may be energized from the
battery supply, even when the
input ac power is disconnected.

6.0 Operating Instructions

Risk of electrical shock—
SDU Series Instruction Manual • 9

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Sdu 500Sdu 850Sdu 500-5Sdu 850-5500850 ... Mostrar todo

Tabla de contenido