Installation and assembly

4
Installation and assembly
CAUTION
Risk of burns
Escaping hot medium can cause burns.
Maintain a sufficient distance from the escaping medium.
Wear suitable personal protective equipment (safety gloves and goggles).
4.1

Notes

The following items must be considered when assembling and installing the equipment:
Do not install the device above sensitive components or close to electrical plant.
Perform installation in dry and frost-proof locations.
The flow direction is not pre-determined.
The component is intended for vertical installation with standard installation lengths F1(DIN 3202-1) according to DIN EN 558:2012-
03.
When installing ensure there are no residual stresses.
Any stresses that may occur in some cases must be countered by appropriate constructive actions. Stresses may be caused by
temperature effects, for example.
Ensure the device is readily accessible in its place of installation.
Ensure sufficient bearing capability of the installation site.
This applies to filling the separator with water in particular.
If necessary additional structural measures may be required to ensure adequate load bearing capacity.
The device is not a load-bearing structural element.
By default, the calculation of the vessels does not take lateral acceleration forces into account. Avoid alternating stresses such
as pressure shocks, abrupt pressure changes, or strong vibrations.
Use only approved transport and lifting equipment.
After installing insulation, attach the (adhesive) nameplate on the outside so that it is readily visible.
Flush the system thoroughly after installation.
Note!
Observe the correct positioning of the add-on components so that they function correctly.
We recommend fitting shut-off valves upstream and downstream of the device to simplify maintenance.
Note!
Consider the static forces acting on the pipe system with reference to the force moments when installing in vertical
pipelines.
10 — English
Reflex Exvoid/Exdirt V — 06.2017