Installation
7.3
Configuration of unit software
Before you first start up the unit, the controls can be adapted to suit the
installation conditions. This must be done by the person installing the unit.
In configuration mode, the following unit software parameters must be set
at the control panel (fig. 0, page 8).
Menu
Parameter
level
1
Set temperature
2
Low voltage
cut-off
3
Operating mode
4
Default settings
5
Temperature unit
display
I
NOTE
Configuration mode can still be activated if the undervoltage protection
mechanism has switched off the unit and only residual voltage is
available.
7.3.1
Starting and ending configuration mode
The adjustable parameters can be changed in configuration mode:
➤ When using the ON/OFF (fig. 0 1,page 8) button to switch on the
unit, hold both buttons + and – (fig. 0 6 and 7, page 8) pressed until
the compressor LED flashes.
✓ You are now in configuration mode.
✓ The display version (e. g. "3.1S") appears in the digital display
(fig. 0 5,page 8) for 2 seconds.
✓ The first digit of the digital display (fig. 0 5,page 8) shows the menu
level and the second and third digits show the parameters which can
be set, e.g.
I
NOTE
If you make no entry on the control panel for 60 seconds, the unit quits
configuration mode and shuts down.
➤ Press the ON/OFF button to quit configuration mode.
48
Meaning
The unit starts at the temperature
defined here.
The battery monitor shuts down the unit
at the voltage defined here.
The unit starts with the operating mode
defined here.
Parameters 1 – 3 can be reset to the
default settings.
The temperature can be displayed in °C
or °F.
for menu level 1 and a set target value of 17 °C.
1.17
CoolAir RT880, SP950T
Default
setting
20 °C (68 °F)
Characteristic
figure 4 =
22,8 V
0 = Automatic
mode
--
°C