7 LIST OF CODED ERRORS

Error
code
Er02
Incorrect wiring or connection error: L and PE reversed
Er03
Incorrect wiring or connection error: L missing
Er04
UF voltage too high on earth electrode (danger): measurement STOPPED
Er05
The calculation (current measured by the probe) by (the measured voltage) is too low
Er06
The current measured by the probe is too unstable
Er07
Earth potential too high (potential danger): measurement STOPPED
Untimely interruption of the current during the measurement of Z
Er08
breaker tripped?) - Probable cause: reversal of conductors N and PE or the installation
leakage current is too high
Er10
Voltage too high on the voltage probe (danger): measurement STOPPED
Er18
Current probe not connected
Er24
Backup memory full (action: delete stored data)
C.A 6454 loop tester
Delivered in a carrying bag containing:
- 1 measuring cable for Euro mains socket,
- 1 measuring cable, 3 separate leads,
- 3 crocodile clips (red, yellow, and white),
- 3 contact pins (red, yellow, and white),
- 1 pouch with neck strap
- 1 optical communication cable
- data processing software program
- 6 LR6 batteries (1.5V)
- 1 user manual in 5 languages
ACCESSORIES
- C172 current probe
- C174 current probe
- MN20 current probe
- serial printer
- Earth set (1T earth testing rod + one 30m long green lead on reel
+ a reinforced carrying case)
Meaning

8 TO ORDER

73
or Z
(earth fault
LN
LPE
P01123511
P01120310
P01120330
P01120440
P01102903
P01101999