Connect the telephone/modem lines
A single telephone or modem line may be connected to the jacks that protect against overvoltage on the rear
of the UPS. The modular RJ-45/RJ-11 jacks are compatible with standard single telephone connections.
Connection to the line protection jacks requires a telephone extension cable (supplied).
N.B.: The connection is optional. The telephone/modem line protection is effective even if the UPS is
switched off or disconnected from the mains.
Warning: The overvoltage protection device for telephone lines may not work if it is not installed
correctly. Make sure that the telephone wall cable is inserted in the connector marked "IN" and that the
cable of the unit to be protected (telephone, modem, etc.) is inserted in the connector marked "OUT".
Warning: The overvoltage protection device is only for use in closed environments; do not connect
telephone wires during a storm
N.B.: The protection device limits the effects of overvoltage, but does not guarantee total protection.
FUNCTIONING
Switching on
After connecting the UPS to the mains outlet, press the on/off switch to turn the UPS on. The switch will
remain pressed and the "NORMAL LINE" LED will come on.
The UPS can be switched on even in the event of a power failure.
Switching off
Press the on/off switch again. It will return to the rest position and the "NORMAL LINE" or "BATTERY
MODE" LED will go off.
Self Diagnostic "BATTERY TEST" ( via software)
(only for 40 Plus – 55 Plus – 65 Plus models)
Use the self-diagnostic battery test (refer to the enclosed software guide) to test the battery conditions. In
normal power supply status and with charged batteries, run the "Test Battery" command. The UPS will
perform the self-diagnostic test.
N.B.: During the test, the UPS will briefly power the loads from the batteries.
If the self-diagnostic test is completed successfully, the UPS will return to mains power after a few
seconds.
If the test fails, mains power is restored immediately to the UPS and the "Replace batteries" LED comes
on. The loads are not affected. Charge the battery for 6-8 hours and repeat the test. If the "Replace
batteries" LED remains on, call the nearest distributor for replacement batteries.