Voltage Test; Low Voltage Mode; Voltage Interference Suppression (Vis); Continuity Test - Nieaf-Smitt EazyVolt Pro Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41
The torch light automatically switches off after approx. 30 sec.
7.3

Voltage test

Connect both probes to the object under test
The voltage is indicated by LED or LCD
- Buzzer sounds when a threshold voltage is >50 V AC/DC or
>120 VDC
- Vibration is ON when a threshold voltage is >50 VAC or
>120 VDC (EazyVolt Pro LCD only)
Voltage polarity is indicated in following manner:
Pro LED
-
AC: + and -6 V LED are both on
-
+DC: +6 V LED is on
-
- DC: -6 V LED is on
Pro LCD
-
AC: AC symbol is on
-
+DC: +DC symbol is on
-
-DC: -DC symbol is on
Once the tester is powered on, it will automatically measure vol-
tage in the range of 6 V-690 V (Pro LED) and 6 V-1000 VAC/1500
VDC (Pro LCD in voltage/continuity mode) and 1 V-1000
VAC/1500 VDC (Pro LCD in low voltage mode)
When the L2 probe + is the positive (negative) potential, the
Polarity indication LED indicates '+DC' ('-DC')
In case of empty batteries: 50/120/230/400/690 V LEDs still
indicate the presence of voltage (Pro LED) or the ELV LED lights
up >50 VAC, >120 VDC (Pro LCD)
7.4
Low Voltage mode (1 V-1000 VAC/1500 VDC - Pro LCD)
Short press the
repeat short pressing until LO symbol is shown on LCD
In Low Voltage mode it is possible to measure AC and DC
voltage from 1 V
Connect both probes to the object under test
Continuity mode is disabled in Low Voltage Mode.
7.5

Voltage Interference Suppression (VIS)

A voltage can be induced by a capacitive or inductive coupling
with a LIVE circuit. This could lead to an Interference Voltage
detection. By pressing the
voltage measurement the Pro LCD will apply a load to the system
to supress this Interference Voltage. A beeping sound will be
heard.
This will increase the detection capability of the presence of
voltage
7.6

Continuity test

Make sure the object under test isn't live.
Connect both test probes to the object under test
-
Continuity test is performed automatically except in Low
Voltage and Resistance mode of Pro LCD
-
Buzzer/Continuity LED lights up and buzzer sounds
continuously to indicate continuity
-
LCD display show Con Symbol to indicate continuity
-
Tester switch to voltage measurement if voltage is
detected during continuity testing >6 V
This test is only possible when batteries are installed and in good
condition
7.7

Diode test

Make sure the object under test isn't live.
Switch into diode testing mode by short pressing two times
button or repeat short pressing until
LCD. Connect both test probes to the diode under test
-
Continuity LED lights up, buzzer sounds continuously and
Con symbol on LCD is on if L1 tip is connected on Anode
of diode and L2 tip on Cathode
-
Continuity indication will be off if L1 tip is connected on
Cathode of diode and L2 tip on Anode
button once to enter Low Voltage Mode, or
RCD/ LOAD
www.nieaf-smitt.com
buttons
during an AC
symbol is shown on
7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Eazyvolt pro ledEazyvolt pro lcd

Tabla de contenido