IS 18 - 21 - 24 - 27
GB
the generator must be carried out with the engine off
and leaving it to cool down sufficiently, and must
only be carried out by authorised and suitably trained
personnel.
disconnect one pole of the starter battery in order to
prevent accidental starting.
GB
- 20
Any maintenance operation on
Before accessing the generator,
Check the oil level by means of the
graduated dipstick [Fig. 7, Ref. 2]. The level must
always be between the MAX and MIN notches on the
dipstick [Fig. 7 Ref. 1].
- The first engine oil change must be carried out after
50 hours of generator operation. For the second
and subsequent oil changes, every 200 hours is
sufficient.
- For more detailed information on engine
lubrication, consult the engine use and maintenance
manual attached to the generator.
- Dispose of the used oil or fuel in an appropriate
manner as they are polluting products.
Take the used engine oil to special collection
centres responsible for disposal.
Avoid contact of engine oil with
the skin. During maintenance operations use gloves
and protective glasses.
For the safety of the engine, use
only original spare parts.
When the operation has been
completed, thoroughly wipe off all oil and fuel from
the engine parts.