Start up
­ Setting data table ­ Air regulation
burner output
kW
1° stage
2° stage
1° stage
205
274
1,6
239
331
1,3
274
388
burner output
kW
1° stage
2° stage
1° stage
205
296
1,5
262
388
1,3
308
479
1,4
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
B
420010537801
pressure in
combustion
chamber
oil output
mbar
kg/h
2° stage
1° stage
2° stage
3,3
18
3,7
21
1
4
24
pressure in
combustion
chamber
oil output
mbar
kg/h
2° stage
1° stage
2° stage
3,5
18
4
23
4,7
27
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
Air damper setting (A).
Remove the cover to gain access to the
adjustment cams. The cams are adjusted
using the screwdriver.
Descrıption:
I
- Limit switch for the "HIGH FLAME"
position of the air damper
(MAX POWER).
II
- Adjusting cam for the air damper
position at shut down (0°).
III - Auxiliary switch for the release of the
second stage valve (HIGH FLAME).
IV - Limit switch for the "LOW FLAME"
position of the air damper.
Firing head setting (B).
Slide the burner out off mounting flange.
Modify air cilynder position (1,2,3,4) as
shown in fig.B using a screwdriver. Slide
again the burner in the mounting flange
end fix to the boiler.
Maxflam 30 AB
nozzle 60° HO
1° stage
2° stage
24
3,00
1,00
29
3,50
1,50
34
4,00
2,00
Maxflam 50 AB
nozzle 60° HO
1° stage
2° stage
26
3,00
1,50
34
4,00
2,00
42
4,50
2,50
pump
pressure
firing head
air damper setting
bar
setting
1° stage
23
1
18°
23
2
20°
23
3
20°
pump
pressure
firing head
air damper setting
bar
setting
1° stage
23
1
15°
22
2
20°
23
3
20°
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Note : Cam III (to enable the stage two
electrovalve to open) is adjusted to an in-
termediate position between the low flame
and high flame positions (to an angle ap-
proximately 5° greater than the low flame
position).
www.ecoflam­burners.com
EN
stage
30°
40°
60°
stage
40°
50°
50°
15