Page 10
ENGLISH
Connect to AquaLink RS RS-485 Connector
(or Multiplexer Interface Board)
S1
S2
4-Position
DIP Switch
Figure 5.
Wiring AquaLink RS, PDA or Z4
3.2.4.2 Install with JEP-R variable-speed
controller
IMPORTANT
The installer must TURN ON switches 1 and 2 at the
VS Plus HP pump when connected to the variable-
speed controller.
1. Disconnect the high voltage lines or open any
breaker to which the pump power is connected.
WARNING
ELECTRICAL SHOCK HAZARD
Turn off all switches and the main breaker in
the variable-speed pump electrical circuit before
starting the procedure. Failure to comply may
cause a shock hazard resulting in severe personal
injury or death.
2. Remove the junction box cover and feed the
RS-485 cable into the fi tting.
3. Unplug the RS-485 connector.
4. Attach the four (4) RS-485 cable wires to the
RS-485 connector. Match the wire colors with the
positions on the connector: See "Figure 6. Wiring
JEP-R VSP Controller"
Jandy
Pro Series VS PlusHP Pumps
®
4 3 2 1
4 3 2 1
6 5 4 3 2 1
10 9 8 7 6 5 4 3 2 1
RS6 & RS8 ONLY
RS8 ONLY
POOL MODE
RESET
SPA MODE
AUTO
SPA DRAIN
SERVICE
HEATER
SOLAR
SPA FILL
TIME OUT
4 3 2 1
4 3 2 1
Variable-Speed
Pump
|
Installation & Operation Manual
5. Insert the RS-485 connector back into the junction
box.
6. Dip switches 1 and 2 must be in the ON position,
and switches 3 and 4 must be in the OFF position.
See "Figure 6. Wiring JEP-R VSP Controller"
4-Position
DIP Switch
Figure 6.
Wiring JEP-R VSP Controller
7. Connect the other end of the cable to the
controller. Match the colors of the wires with the
appropriate connector positions. See "Figure 6.
Wiring JEP-R VSP Controller"
8. Restore power and verify the operation of the
controller.
9. Refer to the Variable-Speed Controller Owner's
Manual, H0412200, to operate the pump.
3.2.4.3 Pump Dip Switch Settings
As shown in Figures 5 and 6 the 4 position dip switch
serves two (2) functions: it selects the pump address,
and it determines what type of controller will be used
with the pump.
Table 2.
Dip Switch Settings
Switch 1 Switch 2 Controller
OFF
OFF
Factory Default
OFF
OFF
AquaLink
or AquaLink Z4
ON
ON
Variable Speed Controller
Switch 3 Switch 4 Pump Address
OFF
OFF
PUMP 1 (Factory Default)
ON
OFF
PUMP 2
OFF
ON
PUMP 3
ON
ON
PUMP 4
Controller
(Rear View)
5 4 3 2 1
4 3 2 1
RS485
REMOTE CONTROL
4 3 2 1
Variable-Speed
Pump
RS, AquaLink PDA,
®