Installation • Instalación
Installation • Instalação
1.77"
(45)
dia 0.26"
ø 6,5
1" (DN25)
½" connector must not be removed
Conector de ½", no debe retirarse
1" (DN25)
½"(DN13)
12
Multiple inlet adapter
Adaptador de conexión
1" (DN25)
½"(DN13)
Collecting line
Tubo colector
Flow splitter
Distribuidor de
condensado
Area of installation
• Sealed floor or collecting basin 18
gallons!
It is crucial to ensure that untreated con-
densate or oil cannot get into the sewer
system in the event of damage.
• The floor area must be stable and level
(max. inclination 1°) to ensure reliable
functioning of the KCF.
With the multiple inlet adapter, up to 3
condensate lines can be connected di-
rectly to the KCF unit.
The inlet adapter can be mounted on the
1" (DN25)
wall. It has three ½" hose connectors for
inflow from the ECO-DRAIN and one 1"
hose connector for the hose to the KCF.
The ½" connector on the KCF must not
be removed.
The 1" hose can be pulled over the ½"
connector. Refer to page 10
If there are more than 4 feed points, it
will be necessary to install a header of
1" diameter above KCF inlet (height 24"
above floor) with a slight slope down to
the KCF unit (min. 1°)
Up to 4 KCF units can be joined to a flow
splitter.
• Feed in the condensate
top
1" (DN25)
½"(DN13)
Waste water drain
• Must be lower than the water outlet of
the KCF
• Install a trap against odours
Connecting the waste water hose:
• Use the hose supplied and attach it to
the KCF water outlet.
• Lay the hose with a continuous slope
down to the waste water drain (trap).
english
from the
KCF 100