Setting the set point (desired temperature) 
Press SET for 1 sec the set value will start flashing after a few moments. 
Increase or decrease the value using UP or DOWN. 
Press SET to confirm the new value. 
 
Switching the device ON/OFF 
Press UP for more than 3 sec. The control and defrost algorithms are now disabled and the instrument 
displays the message "OFF" alternating with the temperature read by the set probe. 
 
Manual defrost (models S, X, Y and C only) 
Press for DOWN more than 3 sec (the defrost starts only the temperature conditions are valid). 
 
 
Continuous cycle (models S, X, Y and C only) 
Press UP and DOWN together for more than 3 sec. 
 
Access and setting type F (frequent) and type C (configuration) parameters 
1. Press SET for 3 sec (the display will show "PS") 
2. To access the type F and C parameter menu, enter the password "22"using UP/DOWN; 
To access the F parameter menu only, press SET (without entering the password); 
3. Scroll inside the parameter menu using UP/DOWN; 
4. To display/set the values of the parameter displayed, press SET, then UP/DOWN and finally SET to 
confirm the changed (returning to the parameter menu). 
To save all the new values and exit the parameter menu, press SET for 3 sec. 
To exit the menu without saving the changed values (exit by timeout) do not press any button for at 
least 60 sec 
 
Table of alarms 
Alam 
buzzer and 
code 
alarm relay 
E0 
active 
E1 
inactive 
E2 
inactive 
IA 
active 
dOr 
active 
LO 
active 
HI 
active 
EE 
inactive 
EF 
inactive 
Ed 
inactive 
dF 
inactive 
cht 
inactive 
CHT 
active 
EtC 
inactive 
 
Our products have been precissely modified before leaving factory. To avoid damaging compressor unit or 
other malfunctions, users must not modify the microcomputer parameters privately. 
 
J
.P. SELECTA s.a.u.
CÓDIGO 80404 REV 0
LED 
Description
ON 
probe 1 error=control
ON 
probe 2 error=defrost
ON 
probe 3 error=condenser
external alarm
ON 
open door alarm
ON 
low temperature alarm
ON 
high temperature alarm
ON 
unit parameter error
ON 
operating parameter error
ON 
defrost ended by timeout
ON 
defrost running
ON 
condenser dirty pre‐alarm
ON 
condenser dirty alarm
ON 
clock alarm
ON 
Autovía A-2 Km 585.1 Abrera 08630 (Barcelona) España
e-mail: selecta@jpselecta.es - website: http://www.jpselecta.es
09/2020
Parameters 
involved
[d0=0/1]
[A4=10]
[A4=10][+A7]
[A4=7/8][+A7]
[AL][Ad]
[Ah][Ad]
[dP][dt][d4][A8]
[d6=0]
[A4=10]
[A4=10]
Tel 34 93 770 08 77 Fax 34 93 770 23 62
Pag.: 13