5 Closure types/Locks
Item
EN31.196.060...
EN32.196.120...
EN32U.063.110...
EN91-196-060...
EN92:196-120...
EN92U:067-110...
Fig. 1 The doors close automatically in case of fire.
Fig. 2 Doors with arrest system
Fig. 3 Lockable using a cylinder lock
The products should in general always be kept closed when not in use. The products
can be locked using a lock cylinder to protect against unauthorized access. It should
be noted that the products have no emergency unlock, i.e. that persons can become
locked in the cabinet unable to free themselves unaided!
6 Interior fittings
6.1 Base tray
Pursuant to EN 14470-1:
A base tray must be installed beneath the
lowest setting level. The base tray must
have a minimum collection volume of 10%
of all of the containers stored in the
cabinet or at least 110% of the volume of
the largest individual container depending
on which volume is greater.
Attention:
Use of the base tray as a storage surface
is permissible only in connection with a
perforated plate insert.
28
Closure types/Locks
Fig. 1
ü
ü
ü
ü
ü
ü
Technical changes are reserved!
Fig. 2
ü
ü
ü
ü
-
-
Fig. 3
ü
ü
ü
ü
ü
ü