Apéndice D: Parámetros de Menú
Tabla D.1 Tabla de Compensación de Caída de Voltaje de Línea - Resistencia y Reactancia de Distribución de Línea
Cobre - Estirado en frío
Reactancia (Vea nota 1)
Tam. del
Res. a
Distancia "D" entre centros de conductores
conductor
50°C
MCM
18"
24"
30"
1000
.0685
.449
.484 .511
750
.0888
.466
.501 .529
600
.1095
.481
.516 .543
500
.1303
.492
.527 .554
400
.1619
.507
.542 .569
350
.1845
.515
.550 .577
300
.215
.525
.560 .587
250
.257
.536
.571 .598
AWG
4/0
.303
.546
.581 .603
3/0
.382
.554
.589 .616
2/0
.481
.581
.616 .643
1/0
.607
.595
.630 .657
1
.757
.609
.644 .671
2
.964
.623
.658 .685
4
1.518
.648
.683 .710
6
2.41
.677
.712 .739
8
3.80
.714
.749 .776
Nota: 1. La Reactancia a 60 hercios en ohmios por milla de cada conductor de una fase, o de 3 fases, espaciamiento triangular simétrico. Vea a
continuación otros arreglos de conductores. La reactancia para otras frecuencias es F/60 veces los valores de la tabla. Los valores de
reactancia son para conductores de cobre estándar concéntricos y son aproximadamente correctos para conductores de cable de aluminio.
El software Calculador de Caída de Voltaje de Línea de Siemens simplifica
el cálculo de estos parámetros. Simplemente ingrese los valores del
sistema y el software calcula automáticamente los componentes resistivos
y reactivos. Ingrese estos valores en el menú <REGULATOR> del
L
L
MJ-X
, y el MJ-X
compensa automáticamente la caída de voltaje de
línea cuando se ajusta el voltaje de salida del regulador.
58
Omhios por Conductor por milla a 60 Hz
36"
42"
48"
54"
60"
.533
.552 .568 .593
.595
.550
.569 .585 .600
.612
.565
.584 .600 .615
.627
.576
.595 .611 .626
.638
.591
.610 .626 .641
.653
.599
.618 .634 .649
.661
.609
.628 .644 .659
.671
.620
.639 .655 .670
.682
.630
.649 .665 .630
.692
.638
.657 .673 .688
.700
.665
.684 .700 .715
.727
.679
.698 .714 .729
.741
.693
.712 .728 .743
.755
.707
.726 .742 .757
.769
.732
.751 .767 .782
.794
.761
.780 .796 .811
.823
.798
.817 .833 .848
.860
B
A
C
Aluminio - Reforzado con acero
Reactancia (Vea nota 1)
Tam. del
Res. a
Distancia "D" entre centros de conductores
conductor
50°C
MCM
18"
24"
1272.0
.0851
.421
.456 .483
954.0
.1128
.439
.474 .501
795.0
.1373
.450
.485 .512
556.5
.1859
.469
.504 .531
477.0
.216
.479
.514 .541
397.5
.259
.490
.525 .555
336.4
.306
.500
.535 .562
266.8
.385
.514
.549 .576
AWG
4/0
.592
.630
.665 .692
3/0
.723
.670
.705 .732
2/0
.895
.690
.725 .752
1/0
1.12
.705
.740 .767
2
1.69
.714
.749 .776
4
2.57
.708
.743 .770
6
3.98
.722
.757 .784
A
B
3
D =
A B C
C
Contacte su representante de Siemens para obtener este software. Este
software también se puede descargar del sitio web de Siemens. Vaya a
www.siemenstd.com, seleccione Products, y luego el ítem Voltage
Regulator. Esta aplicación está disponible en la página Download
(Descargar).
Siemens Power Transmission & Distribution, Inc.
30"
36"
42"
48"
54"
.505
.524 .540 .555
.523
.542 .553 .573
.534
.553 .569 .584
.553
.572 .588 .603
.563
.582 .598 .613
.574
.593 .609 .624
.584
.603 .619 .634
.598
.617 .633 .648
.714
.733 .749 .767
.754
.773 .789 .804
.774
.793 .809 .824
.789
.808 .824 .839
.798
.817 .833 .848
.792
.811 .827 .842
.806
.825 .841 .856
60"
.567
.585
.596
.615
.625
.636
.646
.660
.776
.816
.836
.851
.860
.854
.868