ENGLISH
Installation and assembling:
To ensure adequate cooling, the device must be installed vertically, with the input and output terminals at the bottom. Be
sure to leave a minimum free space of 50 mm (2 in.) above and below the device. The supply voltage (120/230 V AC)
must be connected in accordance with IEC 60364 and EN 50178. A protective device (fuse) and an insulating device for
disconnecting the power supply must be provided.
In Ex - applications must be guaranteed that installation is according to protection class IP 54.
Danger:
!
The mains switch has to be switched off and prevented from being switched on again before installation or maintenance.
If these rules are not adhered to, contact with live parts or improper use can result in death or severe personal injury.
Description and construction:
The SITOP 24 V/2.5 A, 5 A, 10 A power supplies are rail-mounted built-in units. The relevant DIN/VDE regulations or
equivalent local regulations must be observed during installation.
Primary switched-mode power supply for mounting on a DIN EN 50022-35x15/7.5 standard.
For connection with firm wiring to 120 or 230 V, 50/60 Hz single-phase AC system.
Output voltage +24 V DC, potential-free, protected against short-circuit and open-circuit conditions.
Parallel connection of two similar devices to increase the power is permitted (provided the difference
of the output voltages is < 0,2 % and the line impedances are equal to the load).
Technical specifications:
Specifications valid for input voltage 230 V AC and ambient temperature +25 °C, unless otherwise stated. They are subject
to change without prior notice.
Type:
Order no.:
Input:
Rated voltage V
:
in
Voltage range:
Line frequency range:
Mains buffering:
Rated current I
in:
Protection in the mains supply line:
Output:
Rated voltage V
:
out
Residual ripple/spikes:
Setting range:
Rated current I
:
out
- range up to 60 °C at ≤ 24 V DC
- range up to 50 °C at > 24 V DC
- range up to 45 °C at ≤ 24 V DC
- range up to 35 °C at > 24 V DC
Current limitation:
Dynamic current limitation:
Efficiency at full load:
Enviromental conditions:
Transportation and storage
temperature:
Ambient temperature during
operation:
Degree of protection:
Pollution degree environment:
Humidity rating:
EMC interference emission:
EN 55022:
EMC interference immunity:
Safety:
Protection class:
Galvanic insulation
primary/secondary:
Certificates:
CE
UL/CSA
Approval for Shipbuilding
Directive 94/9/EC
C-Tick
Siemens AG Österreich
24 V/2.5 A
24 V/5 A
6EP1332-2BA10
6EP1333-2BA01
120/230 V AC
85-132/170-264 V AC
47...63 Hz
> 20 ms
1.1/0.65 A
2.1/1.15 A
3 A Char. C
6 A Char. C
24 V DC
< 150/240 mV
pp
22,8...28 V DC
2.5 A
5 A
0...I
out
0...I
out
0...1.2xI
out
0...1.2xI
out
typ. 3.3 A
typ. 6.5 A
3.75 A/5 sec
7.5 A/5 sec
typ. 84 %
typ. 87 %
-40 °C...+85 °C
0 °C...+60 °C
IP 20
2
Climate category 3K3 acc. to EN 60721, relative air humidity 5...95 %, without condensation
EN 61000-6-3
EN 61000-6-3
Class B
EN 61000-6-2, EN 61000-4-2/-3/-4/-5/-6/-11
I
SELV output voltage acc. to EN 60950 and EN 50178, Transformer corresponds EN
61558-2-17, Protection against overvoltage at internal failure: V
Version 2)
CE marking acc. to 98/336 EEC and 73/23 EEC
UL 508 (Listed, File E197259), CSA C22.2 No 14, No 60950-1-03
Germanischer Lloyd
Conformity statement EN 60079-15: ATEX94/9/EC Kat.3;Eex, nA, II, T4 U
AS/NZS 2064:1997
24 V/5 A
6EP1333-2AA01
typ. 87 %
EN 61000-6-4
4/8
24 V/10 A
24 V/10 A
6EP1334-2BA01
6EP1334-2AA01
4.1/2 A
4.1/2.4 A
10 A Char. C
10 A
typ. 13 A
15 A/5 sec
typ. 91 %
typ. 90 %
EN 61000-6-3
EN 61000-6-4
< 33 V (from
out
SITOP smart