5 Technical data
5 Technical data
Hydraulic separator
Dimensions
Pipe connections bottom
Pipe connections top
Centre distance (flow / return)
Installation height
Width
Height
Technical data
Maximum admissible pressure
Max. admissible temperature
Recommended range of application up to:
corresponds to (for ΔT = 20 K)
Materials
Fittings / body
O-rings / gaskets
Insulation
6 Scope of delivery [specialist]
See last pages of these instructions
2017/01
MW25
1½" ext. thread /
1" int. thread
1" PAW flange
for 1½" nut
375 mm
195 mm
600 mm
150 mm
6 bars
110 °C
3 500 l/h
80 kW
993x4213-mub-ml – V01
MW25/32
2" ext. thread /
1¼" int. thread
1¼" PAW flange
for 2" nut
375 mm
200 mm
600 mm
150 mm
6 bars
110 °C
4 800 l/h
110 kW
Brass
EPDM / AFM 34
EPP
B-7