Description
RMS Deviation
Subtraction of 1
cycle RMS from
adjacent cycles.
Used for cyclic
waveshape
transient trigger
system.
Maximum magnitude
value of Crest.
Largest Absolute
magnitude of
samples in a ½
cycle. Used for cyclic
waveshape transient
trigger system.
Phase of
fundamental on
individual cycle.
Derived from DFT
output based on sync
channel.
Phase of
fundamental
averaged over
200ms.
Derived from DFT sine
expansion output.
* +/- 0.05 % of FS for input < 40 V
GMC-I Messtechnik GmbH
Abbreviation
Wiring Configuration
Vcycw-a
Single phase
Vcycw-b
Split phase
Vcycw-c
Wye
Vcycw-d
Vcycw-ab
Measured for Delta
Vcycw-bc
Not Calculated for Wye
Vcycw-ca
Vpk-a
Single phase
Vpk-b
Split phase
Vpk-c
Wye
Vpk-d
Vpk-ab
Measured for Delta
Vpk-bc
Not Calculated for Wye
Vpk-ca
Vcycdeg-a
Single phase
Vcycdeg-b
Split phase
Vcycdeg-c
Wye
Vcycdeg-d
Vcycdeg-ab
Measured for Delta
Vcycdeg-bc
Calculated for Wye
Vcycdeg-ca
Vdeg-a
Single phase
Vdeg-b
Split phase
Vdeg-c
Wye
Vdeg-d
Vdeg-ab
Measured for Delta
Vdeg-bc
Calculated for Wye
Vdeg-ca
MAVOWATT 230, 240, 270 & 270-400
Formula
Vrms(cycle 1) -
Vrms(cycle 2)
Largest Absolute
magnitude of 256
samples (1/2 cycle)
where g= phase
where n=1 for 1 st har-
monic
where n=1 for 1 st har-
monic
Averaged over 10/12
cycles
Units
Precision
Volts
+/- 0.2% of
Reading *
15 KHz BW
Volts
+/- 0.2% of
Reading *
Degree +/- 1°
Degree +/- 1°
45