Gossen MetraWatt MAVOWATT Serie Guía De Uso página 56

Analizadores de redes
Tabla de contenido

Publicidad

MAVOWATT 230, 240, 270 & 270-400
Description
Individual Inter
Harmonic Voltages
h:h+1
0-127
h0=DC
Individual Inter
Harmonic Current
h:h+1
0-63
h0=DC
Instantaneous
Flicker
Instantaneous Flicker
Low Pass Filter output
stage
Instantaneous Flicker
Square Root output
stage
Instantaneous Flicker
Square Root output
stage LPF
56
Abbreviation
Wiring Configuration
Volts
Current
Pinst-a
All
Pinst-b
Pinst-c
Pinst-ab
Pinst-bc
Pinst-ca
Pinstlpf-a
All
Pinstlpf-b
Pinstlpf-c
Pinstlpf-ab
Pinstlpf-bc
Pinstlpf-ca
Pinstrt-a
All
Pinstrt-b
Pinstrt-c
Pinstrt-ab
Pinstrt-bc
Pinstrt-ca
Pinstrtlpf-a
All
Pinstrtlpf-b
Pinstrtlpf-c
Pinstrtlpf-ab
Pinstrtlpf-bc
Pinstrtlpf-ca
Formula
Computed according to
61000-4-7 using DFT
over 200 mS window
aggregated to selected
journal inter- val as
RMS
Computed according to
61000-4-7 using DFT
over 200 mS window
aggregated to selected
journal inter- val as
RMS
Compliant to
61000-4-15
Compliant to
61000-4-15
LPF - (1 minute TC)
Compliant to
61000-4-15
Compliant to
61000-4-15
LPF - (1 minute TC)
GMC-I Messtechnik GmbH
Units
Precision
Volts
+/- 5 %
Amps
+/- 5 %
None
+/- 8 %
None
+/- 8 %
None
+/- 8 %
None
+/- 8 %

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mavowatt 230Mavowatt 240Mavowatt 270Mavowatt 400

Tabla de contenido