Technical Data
When switching inductive loads, a corresponding protective circuit must be provided for the relay
contacts, e.g. RC circuits. Typical RC combinations for 230 V AC: Capacitor 0.1 µF / 630 V, resistor 100
Ohm / 1 W.
If consumers with an increased switch-on current (e.g. plug-in switched-mode power supply units) are
switched, a switch-on current limitation must be provided.
CAUTION
If line voltage is supplied to one of the terminals XR1-XR3 or XP, no safety extra-low
voltage (SELV) may be connected to any of the other terminals!
Rated voltage (XP):
Maximum current intake:
Internal fuse protection with:
Rated voltage (XP):
Maximum current intake:
Internal fuse protection with:
Rated voltage (XP):
Maximum current intake:
Internal fuse protection with:
Typical AC applications at inductive load
1 Load (e.g. motor pump alpha)
2 RC circuit
Typical RC circuit for 230 V AC:
Capacitor 0.1 µF / 630 V,
resistor 100 Ohm / 1 W
3 Relay contact (XR1, XR2, XR3)
100/200 V AC, 50/60 Hz (D1C D only)
150 mA at 100 V AC
75 mA at 200 V AC
5 x 20 mm miniature fuse
160 mA, 250 V slow-blow
115/230 V AC, 50/60 Hz
100 mA at 115 V AC
50 mA at 230 V AC
5 x 20 mm miniature fuse
160 mA, 250 V slow-blow
24 V DC or 24 V AC, 50/60 Hz
(operation with safety extra-low voltage only!)
250 mA
5 x 20 mm miniature fuse
500 mA, 250 V slow-blow