CAUTION:
To facilitate the adjustment of limit switches, you can remove the aluminum that covers the screw slider.
The profile of the slots can be remove simply by unscrewing the 2 screws that secure the motor hood.
For the end-stop operation, proceed as follows:
• Bring the shutter in position of maximum opening, then lock the mechanical stop by fastening the bolt
• Bring the shutter in position of maximum closing, then position the mechanical stop
STAR 230V (900PS-300FA/900PS-300FA-R/900PS-400FA/900PS-400FA-R)
STAR 24V (900PS300-24FA/ 900PS400-24FA)
MOTOR CABLE
Blue
Brown
Black
Yellow/Green
Gray
ATTENTION:
For encoder operation, when in the closed position, both gate panels must rest against a mechanical stop.
WARNING:
Always connect the earth cable to the mains power earth system with a cable minimum cross sectional
area of 2.5 mm
2
OPERATION END-STOP
ELECTRICAL CONNECTIONS
Capacitor
Motor DX
Opening
Closing
+ encoder
S encoder
- encoder
15
1
Close
2
Open
3
Common
Ground
G
3
1
2
Motor SX
Closing
Opening
+ encoder
S encoder
- encoder