Alarms
A02
Low suction pressure Po
A11
Refrigerant A not selected
A17
High Cond. pressure Pc
A19
Comp. 1 safety cutout
A20
Comp. 2 safety cutout
A21
Comp. 3 safety cutout
A22
Comp. 4 safety cutout
A23
Comp. 5 safety cutout
A24
Comp. 6 safety cutout
A28
Low liquid level
A31
LP common safety
A32
HP common safety
A34
Common fan safety
A35
Air room High temp.
A45
Main switch
A85
High discharge temp. Sd
A86
High superheat Ss
A87
Low superheat Ss
A88
System Critical excep-
tion #1
A89
Manual DI..........
A93
VSD safety cutout
E02
Po sensor error
Ss sensor error
Sd sensor error
Pc sensor error
Sc3 sensor error
Saux1 sensor error
System alarm excep-
tion #1
Alarm Destination
disabled
Alarm Route failure
Alarm Router full
Device is restarting
Common IO Alarm
Manual DO.........
- - 1
AK-PC 710
Minimum safety limit for suction pressore Po has been violated
Refrigerant has not been selected
High safety limit for condensing pressure Pc has been violated
Compressor no. 1 has been cut out on safety input
Compressor no. 2 has been cut out on safety input
Compressor no. 3 has been cut out on safety input
Compressor no. 4 has been cut out on safety input
Compressor no. 5 has been cut out on safety input
Compressor no. 6 has been cut out on safety input
Low liquid level alarm input has been activated
Compressors have been cut out on common LP safety input
Compressors have been cut out on common HP safety input
Common fan safety input has been activated
The temperature measured by Saux 1 sensor is too high
Control has been stopped via the setting "Main Switch" = OFF or via the
external main switch input
Safety limit for discharge temperature has been exceeded
Superheat in suction line too high
Superheat in suction line too low
A critical system fault has arisen – the controller needs to be exchanged
An input has been set in manual control mode via the service tool software
VSD alarm input has been activated
Pressure transmitter signal from Po defective
Temperature signal from Ss suction gas temp. defective
Temperature signal from Sd discharge gas temp. Sd defective
Pressure transmitter signal from Pc defective
Temperature signal from Sc3 air on condenser defective
Signal from extra temp. sensor Saux1 defective
A minor system fault has arisen – power OFF/ON the controller
When this alarm is active the alarm transmission to the alarm receiver
has been disabled. When the alarm is cancelled the alarm transmission is
enabled
Alarms can not be send to the alarm receiver – check the communication
to controller/alarm receiver
The internal buffer for alarm has been exceeded. This can happen if the
alarm transmission to the alarm receiver is interrupted – see above.
Restart of controller after a flash update of the software
A communication problem has arised between the controller and the
extension modules – the problem should be checked immediately
An output has been set in manual control mode via the service tool
software
Iniciación. La pantalla está conectado a salida A. (- - 2 = salida B, etc.)
Control de capacidad RS8FT405 © Danfoss 03-2013