Appendix; Sercos Iii Configuration; Setting Sercos Iii Address (2 Variants); Hardware Addressing (Variant 1) - Aventics DDL Instrucciones De Servicio

Sercos iii
Ocultar thumbs Ver también para DDL:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 145
64
AVENTICS | SERCOS III | R412012613–BDL–001–AC

Appendix

13 Appendix

13.1 SERCOS III configuration

For the PLC configuration software, e.g. IndraWorks, the SDDML
files are required for the bus coupler, as well as each DDL
module used.
This file is not included in the delivery contents and can be
downloaded from the Internet at
www.aventics.com/mediadirectory
The DDL configuration can be read out from the list of the
function groups (IDN/S-0-1302.0.2).

13.2 Setting SERCOS III address (2 variants)

Condition on delivery: default address 53
13.2.1

Hardware addressing (variant 1)

A SERCOS III address between 1 and 127 can be set on the DDL
S SER bus coupler via the S1 and S2 DIP switches. Tab. 9:
SERCOS III addressing contains the values of the individual
switches. To calculate the SERCOS III address, the values must
be added.
Table 9:
SERCOS III addressing
Switches
Bit
S1 (4 bits)
2
S1 (4 bits)
3
S1 (4 bits)
4
S2 (5 bits)
1
S2 (5 bits)
2
S2 (5 bits)
3
S2 (5 bits)
4
Open
On
0
64
0
32
0
16
0
8
0
4
0
2
0
1

Publicidad

Tabla de contenido
loading

Tabla de contenido