4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 20 - fig. 1) indicating the fault
code. Flashing of the arrows (details 18 and 24 - fig. 1) together with the error code indi-
cates which boiler shell is in fault status.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation, press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on
the remote timer control (optional) if installed; if the boiler does not restart, it is necessary
to firstly eliminate the fault.
Other faults cause temporary shutdowns (marked with the letter "F") which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
Table. 4 - List of faults
Fault code Fault
Possible cause
No gas
Ignition/detection electrode
fault
A01
No burner ignition
Faulty gas valve
Insufficient gas
supply pressure
Trap blocked
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature
A03
No water circulation in the
protection activation
system
Air in the system
Fume extraction duct safety
Fault F07 generated 3 times
A04
device activation
in the last 24 hours
Fault F15 generated for 1
A05
Fan protection activated
hour (consecutive)
Ionisation electrode fault
Flame unstable
No flame after ignition stage
Gas valve Offset fault
A06
(6 times in 4 minutes)
air/fume ducts obstructed
Trap blocked
The exchanger probe
F07
High fume temperature
detects an excessive tem-
perature for over 2 minutes
The exchanger probe
F07
High fume temperature
detects an excessive tem-
perature for over 2 minutes
Sensor damaged
F10
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Sensor damaged
F11
Return sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F12
DHW sensor fault
Wiring shorted
Wiring disconnected
Probe damaged
F13
Exchanger probe fault
Wiring shorted
Wiring disconnected
Sensor damaged
F14
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
No 230V power supply
Tachometric signal
F15
Fan fault
interrupted
Fan damaged
F34
Supply voltage under 170V Electric mains trouble
F35
Faulty mains frequency
Electric mains trouble
Pressure too low
Incorrect system water
F37
Water pressure switch
pressure
damaged or not connected
Cure
Check the regular gas flow to the boiler and
that the air has been eliminated from the
pipes
Check the wiring of the electrode and that it
is correctly positioned and free of any
deposits
Check the gas valve and replace it if
necessary
Check the gas supply pressure
Check the trap and clean it if necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and operation
of the heating sensor
Check the circulating pump
Vent the system
See fault F07
See fault F15
Check the position of the ionisation
electrode and replace it if necessary
Check the burner
Check the Offset adjustment at minimum
power
Remove the obstruction from the flue, fume
extraction ducts and air inlet and terminals
Check the trap and clean it if necessary
Check the exchanger
Check the exchanger
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the exchanger
probe
Check the wiring or replace the sensor
Check the 3-pin connector wiring
Check the 5-pin connector wiring
Check the fan
Check the electrical system
Check the electrical system
Fill the system
Check the sensor
cod. 3540S576 - Rev. 01 - 02/2015
Fault code Fault
Possible cause
Probe damaged or wiring
shorted
F39
External probe fault
Probe disconnected after
activating the sliding
temperature
Delivery sensor
A41
Sensor positioning
disconnected from the pipe
A42
Heating sensor fault
Sensor damaged
F42
Heating sensor fault
Sensor damaged
Sensor damaged
Cascade temperature sen-
F50
Wiring shorted
sor fault
Wiring disconnected
Controller DBM12 internal
A61
Controller DBM12 fault
error
Controller not connected
No communication between
A62
controller and gas valve
Valve damaged
A63
A64
Controller DBM12 internal
Controller DBM12 fault
A65
error
F66

5. TECHNICAL DATA AND CHARACTERISTICS

5.1 Dimensions and connections

252
200
B
252
A
fig. 41 - Dimensions and connections
A
Model ECONCEPT 51/51i
B
Model ECONCEPT 101/101i
1 =
Gas inlet
2 =
Heating system delivery
3 =
Heating system return
Cure
Check the wiring or replace the sensor
Reconnect the external probe or disable the
sliding temperature
Check the correct positioning and operation
of the heating sensor
Replace the sensor
Replace the sensor
Check the wiring or replace the sensor
Check the earth connection and replace the
controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the earth connection and replace the
controller if necessary.
252
704
35
115
245
270
EN
410
1
2
3
55

Publicidad

loading

Este manual también es adecuado para:

Econcept 101Econcept 51iEconcept 101i