Other Functions; Cancellation Of Auto Power Off Feature; How To Make Measurements; Voltage Measurements - Weidmuller 2608C Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 70

13.Other Functions

Auto Power off
1. Auto power off: approx. 30 minutes.
2. After auto power off, press any button to restart the meter, and
the reading of measurement will be maintained in the display.

Cancellation Of Auto Power Off Feature:

Press and hold the (RANGE) button while rotating function switch
from off to any position to turn the meter on. The auto power off
feature is disabled.
Noto "APO" annunciator is missing from the LCD.

HOW TO MAKE MEASUREMENTS

Before making any measurements read safty precautions. Always
examine the instrument and accessories used with the instrument for
damage, contamination (excessive dirt, grease, etc.) and defects.
Examine the test leads for cracked or frayed insulation and make sure
the lead plugs fit snugly into the instrument terminals. If any abnormal
conditions exist, do not attempt to make any measurements.

Voltage measurements

1. Turn off power to the device under test and discharge all capacitors.
2. Plug the black test lead into the COM input jack on the meter and conne
connect the test lead tip to a grounded point (the reference point for
measurement of voltage).
3. Set the Function/Range switch to the "V
To avoid possible electric shock, instrument damage and / or equip-
ment damage, do not attempt to take any voltage measurements if the
voltage is above 1000Vdc / 750Vac. 1000Vdc and 750Vac are the
maximum voltages that this instrument is designed to measure.
2608C.p65
/ V
WARNING
26
26
" position.
9427370000_00/06.2019
? 2 009/6/5, 下午 04:18

Publicidad

Tabla de contenido
loading

Tabla de contenido