7.4
Installation and commissioning certificate
Data shown on the nameplate:
Type:
Manufacturing number:
This device has been installed and commissioned in accordance with the instructions provided in the operating manual. The settings in the controller
match the local conditions.
Note!
When any factory-set values of the device are changed, you must enter this information in the Maintenance certificate, see
chapter 10.3 "Maintenance certificate" on page 19 .
For the installation
Place, date
For the commissioning
Place, date
8
Operation
8.1
Automatic mode
Automatic mode includes the two operating modes continuous degassing and interval degassing.
Note!
The starting time of the degassing processes is specified based on the time at the very first start.
•
To reset and for new setting of the start times, see chapter 9.3 "Reset" on page 17
Continuous degassing
This mode is started during first commissioning by pressing the Auto button. Multiple degassing cycles without pause times are carried out over a fixed
period of several hours during the day. The daily start time is set based on the time of the initial commissioning.
Interval degassing
This mode comprises repeating intervals. There is a pause time between the intervals. Once continuous degassing has completed, interval degassing
starts automatically.
8.2
Stop mode
On the controller, press 'Stop' to activate stop mode. The Auto LED of the operating panel goes out, the Stop LED lights up.
Except for the display of information, the device is non-functional in Stop mode. Function monitoring is stopped. The vacuum pump is switched off.
Note!
The system triggers an error message if Stop mode is activated for more than 4 hours.
8.3
Recommissioning
Note!
Recommissioning after a long shut-down takes place by pressing the 'Auto' button.
P
0
P
SV
Company
Company
Servitec Mini — 01.08.2017 - Rev. B
Signature
Signature
Operation
English — 15