Controller
9
Controller
9.1
Operator panel
1
Degassing LED
•
Lights up green during the injection function, see
chapter 4.3 "Function" on page 9 .
2
Water level LED
•
Lights up red if a warning exists
3
Pump LED
•
Lights up green during operation
4
Stop button/LED
•
For stop mode
•
Lights up yellow
5
Auto button/LED
•
For continuous operation
•
Acknowledge error messages
•
Lights up green
6
Error LED
•
Lights up red if an error exists
9.2
Messages
If errors occur during operation of the system, these are visualised via the Error LED in combination with other LEDs.
•
Errors must be acknowledged with the Auto button.
–
Until acknowledgement, the system remains in the error state.
•
Warnings need not be acknowledged. The system continues to run.
–
As soon as the cause of the warning is cleared, the corresponding LED goes out.
Error table
ER Code
Error
02.1
Error LED and Water level
LED light up
(low water)
08
Error LED lights up
14
Error LED and Degassing
LED light up
(discharge period)
19
Error LED lights up and
stop LED flashes
(Stop ≥ 4 hours)
16 — English
Cause
•
Dirt trap clogged.
•
Incoming pipe shut-off.
•
Insufficient pressure in the vacuum pump.
•
Parted cable.
–
No connection of the sensor to the
PCB.
•
Degassing pipe closed.
•
Dirt trap clogged.
•
Set value exceeded.
•
Device is in stop mode for more than 4
hours.
Servitec Mini — 01.08.2017 - Rev. B
Remedy
•
Clean the dirt trap.
•
Unblock the incoming pipes.
•
Check the cable connection.
•
Replace defective component.
•
Open the degassing pipe.
•
Clean the dirt trap.
Set the controller to Automatic mode.