Safe Use Instructions – ROC800-Series
Wiring an FFI into the ROC827
If you need to include a F
as an integral part of a Series 2 ROC827 (shown in Figure
9), wire the FFI to the ROC800 as shown in Figure 7.
Figure 7. ROC827 and FFI Wiring (FFI included in ROC827
Terminal Blocks
BAT+ and BAT–
CHG+ and CHG–
AUX+ and AUX–
AUX
+ and AUX
SW
SW
Terminal Blocks
+ and –
AUX+ and AUX–
Fieldbus Interface (FFI)
OUNDATION
EXTERNAL
POWER
Housing)
Table 1. 12 V DC Power Input Terminal Block Connections
Accepts 12 volts dc nominal from an AC/DC converter or
other 12 volts dc supply.
Analog Input used to monitor an external charging source.
Supplies reverse polarity protected source voltage to external
devices.
Supplies switched power for external devices.
Table 2. 24 V DC Power Input Terminal Block Connections
Accepts 24 volts dc nominal from an AC/DC converter or
other 24 volts dc supply.
Supplies reverse polarity protected source voltage to external
devices.
Note: This is preferred wiring method, since it ensures
that removing power from the ROC800 CPU also
removes power from the FFI.
For more information on operating the FFI, refer to the
F
OUNDATION
D301461X012). For more information on configuring the
FFI, refer to the Field Interface Configurator User Manual
(part D301575X012). For more information on safe use
operation of the FFI, refer to Safe Use Instructions –
F
OUNDATION
Description
Description
Fieldbus Interface Instruction Manual (part
Fieldbus Interface (part D3011666X012).
Volts DC
11.25 to 16 volts dc
0 to 18 volts dc
BAT+ minus 0.7 volts
dc
BAT+ minus 0.7 volts
dc
Volts DC
20 to 30 volts dc
11.3 volts dc
Part D301201X012