6 m
5 m
4 m
3 m
2 m
1 m
- The CICLON CC waste disposer has a Ø32 mm pipe PVC glue socket, or a flexible connection with
clamps which allow adapting to different pipe diameters equipped with a non-return clappet valve. In
case of obstruction, for an easy cleaning of the non-return valve it is recommended to install a shut-
off valve within the vertical discharge pipe that interrupts its emptying.
- Conect the waste pipe or flush as the waste disposer pumps by means of a Ø32 mm pipe, up to a
maximum height of 6 m or to a maximum horizontal distance of 52 m, or a combination of both (see
diagram). A constant 1% minimum slope must be considered up to the discharge point. We
recommend using a 32 mm pipe for optimum performance.
- In combined installations (vertical and horizontal), it must be considered that 1 m. of vertical elevation
is equivalent approximately to a 10 m. horizontal stretch.
- If the installation includes a vertical elevation, the latter must prevail over the horizontal stretch, that
is, every vertical installation must be carried out directly on the waste disposer. The installation of
knees or U-turns result in a pressure head loss that must be subtracted from the maximum pumping
distance (approximately: reduce 1 m. per knee the maximum horizontal distance). Maximum
pumping distances are indicated for a Ø32 mm outlet pipe. Usage of lower dimension pipe results in
reduced pumping distances.
T-604 CC WASTE DISPOSER
Up to 2 m.
Up to 12 m.
Up to 22 m.
Up to 32 m.
Up to 42 m.
Up to 52 m.
Graded range
INSTRUCTIONS AND MAINTENANCE GUIDE - 23