PRINTING OUT EVENTS (with printer connected -optional-)
This menu allows to print out all the events displayed.
1. Press PROGRAMMING to print out.
SEEING HIGHEST LEVELS
This menu allows to list the highest concentration of each group at any date and time.
1.Press PROGRAMMING.
2.Press FORWARD to see highest levels.
3.Press ENTER to exit.
PRINTING OUT HIGHEST LEVELS
This menu allows to print out the maximum concentration of each group.
1.Press PROGRAMMING to print out.
DELETE HIGHEST LEVELS
This menu allows to delete the highest concentrations.
1.Press PROGRAMMING.
"OK" is displayed and an acoustic goes off.
TESTING THE SYSTEM
This menu allows to test the: module line, alarm outputs, relays manoeuvre, power supply and batteries.
1.Press PROGRAMMING.
"User Program" is displayed.
2.Press FORWARD until "System Test" is displayed.
3.Press ENTER to begin or FORWARD to exit of this menu without testing.
A test of the acoustic will be performed and the General Alarm relay will be activated.
The ventilations will be activated according to their programmation.
The voltage provided by the Power Supply -13.8V- and batteries will be displayed. If the battery voltage is
8V, this means that the batteries are not connected or are totally discharged.
You will automatically leave this mode once it has finished.
VENTILATION MODE
This menu allows to choose between the 3 ventilation modes: Automatic, Stop or Manual -continuously activated- for each
group independently. Default programmed ventilation mode is AUTOMATIC.
When going on to the STOP mode without any ventilation status, this circumstance will not be taken into account; and when
the programmed level is reached the ventilation will be activated.
When going on to the STOP mode after the ventilation has taken place, it will remain in that mode as long as the ventilation
status lasts. If it is displayed again it will be rearmed as AUTOMATIC mode.
21
X-maneuro-USU-v03