CLS 100 Plastic
Symptom
Green LED off
Green LED off, with proper sup-
ply
Green LED on and Yellow LED
on while not responding to
product and/or adjustment
Hysteresis region too great
Unequal current in red and
black wire
Yellow LED won't come on or
off
Too much current in loop
Red LED lights opposite to the
Yellow LED when this is not
meant to happen
Red and Yellow LEDs are blink-
ing fast
Red and Yellow LEDs are blink-
ing while switching
Relay contact does not follow
status Red LED
Yellow LED is lit while probe is
not covered
7ML19985QJ81
Cause
Proper power not applied to
device
Power range must equal 12 to
33 V DC at all times
Defective component in
device.
Connector came loose
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times
Proper power not applied to
device
Power range must equal 12 to
33 V DC at all times
Loop circuitry is DC biased
w.r.t. ground
Black wire exceeds + 36 V DC
against Ground
Defective component in
device
Supply voltage too high
Incorrect polarity on red and
black loop terminals
Proper power not applied to
device
Power range must equal 12 to
33 V DC at all times
Proper power not applied to
device
Power range must equal 12 to
33 V DC at all times
Proper power not applied to
device
Power range must equal 12 to
33 V DC at all times
Defective component in
device.
May indicate significant prod-
uct buildup.
Pointek CLS 100 – QUICK START MANUAL
Action
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Contact distributor
Refasten connector
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Correct loop circuitry
Remove cause of voltage on the red wire
and/or bias
Contact distributor
Ensure power range equals 12 to 33 V DC
at all times
Reverse polarity on loop terminals
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Check power source
Minimum 12 V DC on the terminals when
the signal current is 20 mA
Contact distributor
Rotate sensitivity potentiometer further
CCW (counter clockwise). Check sensor
tip
Page EN-13