・System configuration example
* The numbers in the parentheses in the figures below indicate address numbers.
(1) When ME remote controllers are connected
* Move the power jumper from
CN41 to CN40. *
1
* SW5-1: ON *
2
* Leave the power jumper
connected to CN41.
* SW5-1: ON *
2
*1 When a power supply unit is not connected to the centralized control transmission cable, move the power jumper from CN41 to CN40 on
only one of the outdoor units (except TNU model). When the system controller is connected to TB7 side and TNU outdoor unit model is
used, connect a power supply unit to TB7 side. If a power supply unit cannot be used, connect the system controller to TB3 side. Up to
three system controllers can be connected to TB3 side.
*2 If a system controller is used, set SW5-1 on ALL of the outdoor units to ON.
Maximum allowable length of control cables
Transmission cables via outdoor units
Transmission cables
Remote controller cables
*3 When extending the length of the transmission cables to 1000 m (3280 ft), consult your dealer.
WT09452X01
Group 1
Group 3
Ⓐ
Ⓒ
L
+ L
+ L
+ L
1
2
3
L
, L
+ L
, L
1
3
4
ℓ
, ℓ
, ℓ
, ℓ
1
2
3
4
* If the length exceeds 10 m (32 ft), the length that exceeds 10 m (32 ft) needs
to be included in the maximum allowable length of transmission cables
above.
GB-49
Group 5
Ⓑ
, L
+ L
+ L
+ L
, L
+ L
+ L
4
1
2
3
5
1
2
+ L
, L
, L
+ L
≤ 200 m (656 ft)
3
5
6
2
6
≤ 10 m (32 ft)
Ⓐ
Shielded cable
Ⓑ
Sub remote controller
System controller
Ⓒ
≤ 500 m (1640 ft)
*3
6