10-5-2. Fixing the cables in place
Route the cables as shown in the figures below.
・(E)P72 YNU
Main Box
Transmission terminal block
Rubber bushing
(for main inverter connection
wiring (200 V) and unit wiring
(solenoid coil wiring))
Tie band
(Supplied)
Rubber bushing 2
Unit wiring (sensor wiring)
・(E)P72 TNU
Main Box
Transmission terminal block
Rubber bushing
(for Fan cable and unit wiring
(solenoid coil wiring))
Tie band
(Supplied)
Rubber bushing 2
Unit wiring (sensor wiring)
WT09452X01
Main inverter
Transmission cable (not supplied)
connection wiring
The length of the section after the cable
(low voltage)
access hole must be at least 1100 mm (43 in).
Fill the gap.
Main inverter
connection wiring
Transmission cable
(low voltage)
(not supplied)
Fill the gap.
GB-53
Inverter Box
Power supply terminal block
Cable strap
Rubber bushing
(for FAN cable)
Tie band
(Supplied)
Rubber bushing 1
Power cable
(not supplied)
Inverter Box
Power supply terminal block
Cable strap
Rubber bushing
(for FAN cable)
Tie band
(Supplied)
Rubber bushing 1
Power cable
(not supplied)