Rotary Switch; Dip Switch - Victron energy Skylla-i Manual De Usario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

3.1. Rotary switch

The rotary switch provides the user with a selection of preset battery types to be charged. See table below.
Warning: the charge voltages as given below are indicative only. Always refer to the battery supplier for the right
charge voltages.
Pos
Description
0
Do not use
Gel Victron long life (OPzV)
1
Gel exide A600 (OPzV)
Gel MK
Default setting
Gel Victron deep discharge, Gel Exide A200
2
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded), Rolls Solar (flooded)
AGM spiral cell
3
Rolls AGM
PzS tubular plate traction batteries or
4
OPzS batteries in cyclic mode 1
PzS tubular plate traction batteries or
5
OPzS batteries in cyclic mode 2
PzS tubular plate traction batteries or
6
OPzS batteries in cyclic mode 3
Lithium Iron Phosphate (LiFePo
7
Adjustable: maximum charge current and
8
absorption and float voltages can be set with
potentiometers
9
Power supply mode

3.2. DIP switch

The DIP switches are numbered 6 to 1, top to bottom.
Default settings:
DS-6 Bulk Protection
DS-5 Absorption time
DS-4 Absorption time
DS-3 Adaptive
DS-2 Watch
DS-1 Automatic equalization
3.3. Explanation of settings:
DS-6. Bulk Protection. When switched on, the failure LED will be lit and the charger will shut down when the bulk time exceeds
10 hrs.
DS-5 and DS-4. Absorption time. The combination of switches 5 and 4 sets the maximum absorption time in case of adaptive
charging, and a fixed time in case the adaptive mode has been switched off (DS-3).
DS-5
DS-4
Off
Off
On
Off
Off
On
On
On
DS 3. Adaptive. When switched on, the absorption and float time depend on the bulk time (with the maximum time set by DS-5
and DS-4).
The dependencies are as follows:
Absorption time = (bulk time)*20 with a minimum of 30 minutes and a maximum as set by DS-5 and DS-4.
Float time = (bulk time)*20 with a minimum of 4hrs and a maximum of 8hrs.
DS-2. Watch. When DS-2 is on, the battery voltage is checked when the charger is switched on. If the voltage exceeds 26V, the
charger will consider the battery fully charged, and start in storage mode. If the voltage is lower, the charger will start in bulk
mode.
When DS-2 is off, the charger will always start in bulk mode.
Absorption
V
28,2
28,8
29,4
28,2
28,8
30,0
) batteries
28,4
4
Adj.
24,0
on
off
on
on
on
off
Absorption time
2 hrs (preferred for LiFePo
Float
Storage
V
V
27,6
26,4
27,6
26,4
27,6
26,4
27,6
26,4
27,6
26,4
27,6
26,4
n. a.
26,7
Adj.
26,4
n. a.
n. a.
batteries)
4
4 hrs.
8 hrs. (default)
12 hrs.
Equalization
dV/dT
maxV@% of Inom
mV/°C
31,8@8% max 1hr
-32
32,4@8% max 1hr
-32
33,0@8% max 1hr
-32
31,8@25% max 4hrs
-32
32,4@25% max 4hrs
-32
33,6@25% max 4hrs
-32
n. a.
(Vabs. + 3,6V)@25%
max 4hrs
-32
Veq-max < 33.6 V
n. a.
0
0
9

Publicidad

Tabla de contenido
loading

Tabla de contenido