See electrical diagrams (page 185-193)
• Connect the valves from the filter module(s) to the
terminal block between C (C=common) and the
numbered outputs on the control card. Valve control
starts from outlet 1, and so on.
Note! Max. 2 valves/output. See cleaning schedule following
page.
Control box: CONT-B24, CONT-B64, CONT-C24, CONT-C64
TRANSFORMER
120V 208V 230V 400V 460V 575V
LINE SUPPLY
AC1
Control box: CONT-BF24, CONT-BF64, CONT-CF24, CONT-CF64
TRANSFORMER
120V 208V 230V 400V 460V 575V
LINE SUPPLY
AC3
0000100513/011212/0 MDB
CONTROL BOX
MOVE TAP ON PRIMARY SIDE OF
TRANSFORMER TO SUITABLE VOLTAGE.
L1
N
F1
F2
CONTROL BOX
MOVE TAP ON PRIMARY SIDE OF
TRANSFORMER TO SUITABLE VOLTAGE.
U
L1
L2
L3
N
• Remove terminal block and you will find the numbers
printed on the circuit card.
• Connect the equipment to a permanent power feed if
shut-down cleaning is required.
NOTE! LINE SUPPLY: FACTORY SETTING 230V (FOR OTHER
SUPPLY VOLTAGES SEE ELECTRICAL DIAGRAM).
F1
F2
V
W
M
FAN MOTOR
120V - WHITE
208V - BROWN
230V - VIOLET
400V - ORANGE
460V - BLUE
575V - BLACK
120V - WHITE
208V - BROWN
230V - VIOLET
400V - ORANGE
460V - BLUE
575V - BLACK
20