ACCESSORY PARTS NORMALLY AVAILABLE ON THE MARKET AND REQUIRED FOR INSTALLATION
The following items are also required:
- Plumbing unions
- Anti-condensation tape
- Adhesive tape
- Copper pipe of flexible steel pipe with built-in unions
- Ø 8mm press-in plugs
HOW TO INSTALL THE APPLIANCE
The position chosen for the installation must allow the fan fan coil to be easily serviced. It must also ensure access
to the air vent valve at the side of the frame (housed in the wet connections). Proceed in the following way to install
the appliance:
1 . Disconnect the electricity main and make sure that no one is able to connect it again during the installation work.
2 . Remove the intake filter as illustrated in Fig.1 (version VM-B only)
3 . Remove the four screws (1-Fig.1) that fix the casing to the frame. Take out the casing (version VM-B VM-F only).
Make sure to release the connection cable between the receiver card and control card.
4 . If the appliance is to be wall-mounted, use the supplied template to center the holes. Maintain a distance of at
least 100 mm for the VM-B version. If the appliance is to be installed on the floor on feet, comply with the assembly
instructions supplied with the accessory.
5 . For fixing to the wall or ceiling use screw anchors (not supplied) of diameter 8-10mm (2 fig.1).
6 . Make the wet connections. It is advisable to insulate the water pipes or to install trays, available as accessories for
both the horizontal and vertical configurations, to prevent water from dripping when the appliance operates in cooling
mode. The cindensation draining network must be sized to ensure that the pipes slant to a sufficient extent (at least:
1%). If the condensation is drained into the sewers, it is advisable to make a trap to prevent unpleasant odours from
rising back into the room.
7 . Make the electric connections as describerd in the SAFETY REGULATIONS chapter and with reference to the
wiring diagrams in this manual.
8. Fix the case to the frame (VM-B VM-F version only) with the 4 screws (1-Fig.1)
9 . REFIT THE AIR FILTER (VM-B VERSION ONLY).
10 . Hook up the electricity main again.
Fig. 1
34
INSTALLATION