Surroundings
CU 321
Enclosure (CU 321 unit)
Enclosure with fitted NEMA 1 kit
Max. relative air humidity
Ambient temperature
Min. ambient temperature
during full-scale operation
Temperature during
storage/transport
Note: For outdoor installation, the CU 321 must be installed in a minimum NEMA 3R enclosure with provisions
for heating and ventilating designed to keep the CU 321 within its operating temperature limits.
Safeguards
• The CU 321 is protected against short-circuits on
motor terminals U, V, W.
• Monitoring of the intermediate circuit voltage
ensures that the CU 321 cuts out if the intermedi-
ate circuit voltage is too low or too high.
• The CU 321 is protected against ground fault on
motor terminals U, V, W.

7. Pressure sensor voltage chart

Voltage to pressure chart for the CU 321 pressure sensor. Measure DC voltage between "terminal 12" and
"terminal 60", see fig. 18. "Err 2" will appear in the CU 321 display if the signal is outside the range or if the
signal is reversed.
DC voltage
psi
22.5
0.0 to 1.3
22.4
2.5 to 3.8
22.3
5.1 to 6.3
22.2
7.6 to 8.8
22.1
10.1 to 11.4
22.0
12.6 to 13.9
21.9
15.2 to 16.4
21.8
17.7 to 18.9
21.7
20.2 to 21.5
21.6
22.7 to 24.0
21.5
25.3 to 26.5
21.4
27.8 to 29.1
21.3
30.3 to 31.6
21.2
32.8 to 34.1
21.1
35.4 to 36.6
21.0
37.9 to 39.2

8. Disposal

This product or parts of it must be disposed of in an
environmentally sound way:
3 hp, 1- and 3-phase
5 hp, 3-phase
NEMA 0
NEMA 1
DC voltage
psi
20.9
40.4 to 41.7
20.8
42.9 to 44.2
20.7
45.5 to 46.7
20.6
48.0 to 49.3
20.5
50.5 to 51.8
20.4
53.1 to 54.3
20.3
55.6 to 56.8
20.2
58.1 to 59.4
20.1
60.6 to 61.9
20.0
63.2 to 64.4
19.9
65.7 to 66.9
19.8
68.2 to 69.5
19.7
70.7 to 72.0
19.6
73.3 to 74.5
19.5
75.8 to 77.1
19.4
78.3 to 79.6
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
5 hp, 1-phase
NEMA 1
93%
Max. 113°F
32°F
Min. –13°F
Max. 160°F
DC voltage
19.3
80.8 to 82.1
19.2
83.4 to 84.6
19.1
85.9 to 87.2
19.0
88.4 to 89.7
18.9
90.9 to 92.2
18.8
93.5 to 94.7
18.7
96.0 to 97.3
18.6
98.5 to 99.8
18.5
101.1 to 102.3
18.4
103.6 to 104.8
18.3
106.1 to 107.4
18.2
108.6 to 109.9
18.1
111.2 to 112.4
18.0
113.7 to 114.9
17.9
116.2 to 117.5
17.8
118.7 to 120.0
Subject to alterations.
psi