To adjust the bypass level (see page 3, A 3 and A4) press down the bypass setting key (10) and turn the DuoBlend®
bypass blending disc (4) to the level specified in the appropriate tables for Claris standard (chapter 9.1), for Claris
ULTRA (chapter 9.2) and Claris PRIME (chapter 9.3).
After positioning the DuoBlend® bypass blending disc to the specified level, remove the bypass setting key (10) and
hold in safekeeping for possible future DuoBlend® bypass resettings.
5.3 Determining the filter capacity
Based on the carbonate hardness level (for Claris PRIME in combination with the TDS/conductivity and chloride levels)
of the water supply and on your application, use the tables in chapter 9 to identify the resultant filter cartridge volume
capacity based on the recommended DuoBlend® bypass level.
Please mark the bypass setting value together with the installation and replacement dates in the corresponding boxes
on the cartridge label.
5.4
Initial installation
At first identify a suitable place to install the filter system. Note the information provided in chapter 2.
Before you start installing the system, shut off the water supply and disconnect the equipment from the power supply.
Before installation check the filter system and the accessories for any damage – particular attention must be paid when
inspecting the o-rings and gaskets.
After storage below 0° C (32 °F) the filter cartridge must be stored at the ambient temperature of the installation
location for at least 24 hours.
NOTE: The hoses for the supply and discharge line are not supplied as standard but can be ordered as accessories.
A test kit for determining the water hardness is also available as an accessory. You will find more details in section 8.
5.4.1 Installation of filter head / Mounting bracket / Filter cartridge
The system can be operated either free standing or wall mounted in a vertical or horizontal position.
1) If mounting vertically to a wall, securely connect the mounting bracket to the wall using suitable Ø 5mm screws
(#10-12 x ¾" tap screws) (Not included).
Please note: we recommend to install the Claris XXL/ULTRA 2000/Claris PRIME freestanding vertical or horizontal.
If wall mounting of Claris XXL/ULTRA 2000/Claris PRIME is required first firmly attach an additional mounting block
to the wall to allow adequate clearance between the filter cartridge and wall.
2) Install the hoses for the water inlet and outlet to the filter head and respect the following:
• Note the direction of flow – indicated by arrows on the filter head!
• Max. Torque 10 Nm (88 lbf in) on 3/8" BSP threaded connections when using genuine Claris accessory hoses.
• Filter heads with 3/8" BSP threaded connections must only use connecting hoses with flat gaskets. Don't use
hoses or adapter with conical screw for 3/8" BSP connections, they damage the connectors on the filter head and
invalidate any warranty claims.
Filter heads with 3/8" NPT threaded connections must only use connecting hoses with appropriate NPT connection.
Don't use hoses or adapter with inappropriate connections, they damage the connectors on the filter head and
invalidate any warranty claims.
• Only use adaptor nipples of a matching connection type and length to the head connectors, adaptor nipples must
not contact and rest axially on the head. Adaptors of improper design can damage the connections of the filter head
and invalidate any warranty claims.
3) Open the flush/pressure release valve (see page 3, A 6) and direct the flush hose into a suitable container (e.g.
bucket) or to the drain.
4) Turn on the water supply.
5) Insert the filter cartridge into the filter head and turn it clockwise until it stops and the end position is reached. This
vents the system and flushes the filter cartridge.
Flush filter type S,M > 5 l / 1.5 US gal; filter type L,XL > 10 l / 3.0 US gal; filter type XXL > 15 l / 4.0 US gal).
Flush filter type ULTRA 170, 250, 500 > 10 l / 3 US gal; type ULTRA 1000, 1500 > 20 l / 6.0 US gal; type ULTRA
2000 / Claris PRIME > 30 l / 8.0 US gal).
You can check the correct end position of the cartridge. The mark on the filter cartridge must aligne with the larger
recession of the mounting bracket (see page 3, position 8).
6) Close the flush/pressure release valve (see page 3, A 5)
7) After first installation of the filter system the outlet hose and the appliance must flushed. Rinse and vent the hose
and the appliance with a minimum of 2 litre (0.5 US gal). In cases where you can not flush the appliance, remove
the hose from the appliance and rinse it separately.
8) The system is now ready for use. After installing the system and inserting the filter cartridge, check all components
for leaks, water must not escape from any point.
17