Control Specifications; Logic Control Unit; Control Board Diagram; Description Of Terminals - Carrier 30AJ Manual De Instalación, Operación Y Mantenimiento

Unidades enfriadoras de líquidos de condensación por aire
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. CONTROL SPECIFICATIONS

6.1 - LOGIC CONTROL UNIT

Description: Logic control unit for liquid chillers with the
following characteristics:
-
Control panel of the "Soft Touch" type with on/off keys
and indicators of: Power supply, compressor in operation,
timer, protection against freezing and protection by
pressostats.
-
Analog inputs for leaving/return water temperature
sensors.
-
Digital inputs for: Selection of the freezing temperature
(2°C o –7°C), protection pressostat and inlets to control
the distance.
-
Control outlets for the compressor and liquid line
solenoid.
-
Potentiometer to set the temperature and water outlet.

6.2 - CONTROL BOARD DIAGRAM

Connecting
adjustment
temperature
Connecting
front of the
control

6.3 - DESCRIPTION OF TERMINALS

24V, GND : Power supply for the control board,
24Vca - 50/60Hz.
IN 1
: Pressostat input
IN 2
: Power supply for the solenoid valve
IN 4
: Freezing temperature selection: without
connecting it is equivalent to 2°C,
connecting to 24Vca it is equal to –7°C
IN 5
: Remote On/Off: without connecting, the
unit remains off, connecting at 24Vca,
the unit will turn on remotely or locally
depending on the IN6 input.
IN 6
: Remote control activation: Without
connecting, the control is local through
the control front buttons, connecting at
24VCa, the remote control is made
through the IN5 input.
A 3
: Connector for the water temperature
sensor at the chiller outlet (inside
sensor).
A 4
: Connector for the water temperature
sensor outside the chiller (outside
sensor).
OUT1
: Output for the activation of the
compressor contactor.
OUT2
: Output for the liquid line solenoid
activation.

6.4 - CONTROL FRONT BUTTONS AND INDICATORS

To board control
P1
: OFF button.
P2
: ON button.
L1
: Equipment ON indicator.
L2
: Operating compressor indicator.
L3
: Activated anti-cycling timer indicator.
L4
: Anti-freeze device activated.
L5
: Pressostat opening indicator.
L6
: Power supply ON Indicator.
67

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido