Fig. 4.28
Connection of pneumatic hoses to the Panel
Fig. 4.29
•
Drill two holes Ø 10 mm (0.4 in.) in the extraction duct at
the indicated positions (A+B).
•
Connect the pneumatic hose (D) with T-connector (C) to
the extraction duct with the supplied connection material.
A+B
A
B
90°
C
Fig. 4.29 Connection of the pneumatic hose to the extraction duct
5
coMMiSSioNiNg
5.1
general
•
Make sure that the Panel is connected to the mains.
•
Turn the main switch (refer to Fig. 6.1E) to "on". The
system will start up
.
34
•
The HMI starts the installation wizard.
•
Complete the installation wizard.
Select the question mark on the touch
screen for extensive explanation on all
settings.
5.2
Functional tests
5.2.1
Extraction fan
•
Push the START/STOP FAN button (refer to Fig. 6.1F) to
start the fan.
•
Push the button again to stop the fan.
34. Indication: the white LED on the Panel is blinking
0000112606/200917/0 ControlPro
A
Fan Pressure
B
Filter Pressure
A+B
B
D
Panel
?
If any problems or errors occur, refer to chapter 8 /
Troubleshooting.
6
uSE
6.1
Control panel
6.1.1
Panel
The control panel contains the following controls and
indicators:
Fig. 6.1 (also refer to Fig. V on page 83)
A
White LED | POWER ON
- LED off: system is off
- LED blinking: system is starting up
- LED on: system is ready
B
Green LED | FAN RUNNING
- LED off: fan is off
- LED blinking: fan is ramping down
- LED on: fan is running
C
Yellow LED | WARNING
- LED off: no problem
- LED on
: refer to the HMI for the cause of the warning
36
D Red LED | ALARM
- LED off: no problem
- LED on
: refer to the HMI for the cause of the alarm
37
E
Main switch
F
Green button | START/STOP FAN
G Black button | FILTER CLEANING
- to activate an additional filter cleaning cycle
- to suppress the buzzer (push and hold for 5 seconds)
H Rotary switch 0-1 | SERVICE MODE
- 0: normal mode
- I: to lock the touch screen of the HMI for service
purposes
I
Buzzer | acoustic signal
- together with the ALARM signal (D)
- in some cases: together with the WARNING signal (C)
C
D
Panel
E
Fig. 6.1
Control panel
35. Ramp down time: 60 seconds
36. The system continues to run
37. The system stops running
35
A
B
C
D
F
G
H
I
EN - 15