INSTALLATION ON TO THE BOILER
Fix flange 2 to the boiler using 4 screws 3 interposing the insulation gasket 4 and the
possible insulating cord 5. Insert the burner in the flange so that the draught tube pe-
netrates into the combustion chamber by the length suggested by the boiler manufac-
turer. Tighten screw 1 to lock the burner in position.
POSITIONING THE BURNER
We recommend that you fit the burner on the boiler in the position indicated in figures A
and B. Do not assemble in positions C or D otherwise the anti-drip device in the nozzle
holder cannot be used. Above all, positioning here allows good regulation of the air
intake gate and allows its immediate closure when the burner is switched off. Fit the
burner in positions C or D only if absolutely necessary.
IMPORTANT: if the burner is installed in position B the nozzle holder must be rotated
60° so that the notch on the holder is facing upwards. Then lock the burner in place
with the screw and fix the attachment plate with the two upper screws.
UK