Electrical
Plug Pump into
Switch Plug
Sewage
Basin
30"
18"
Figure 1 - Typical Installation
Piping – Effluent Applications
(3/4" or Less Solids)
Piping must be 1-1/2" minimum to carry volume of
pump discharge. Check local codes to determine if a
check valve is required in your system. In cold climates,
check valves are not used to prevent effluent from
freezing in piping.
Piping – Sewage Applications
(2" or Less Solids)
In any case, piping must not be smaller than pump discharge.
When installed in a sewage system, pipe must be capable
of handling semi-solids of at least 2" (5.1 cm) diameter.
The rate of flow in the discharge pipe must keep any
solids present in suspension in the fluid. To meet
minimum flow requirements (2 feet (.6 m) per second in
discharge line), size pipe as follows:
A Pipe Size of
1-1/2" (3.8 cm)
2" (5.1 cm)
2-1/2" (6.3 cm)
3" (7.6 cm)
NOTICE Use PTFE pipe thread sealant tape on pipe
connections. Do not use ordinary pipe joint compound
on plastic pipe or pump. Pipe joint compound can attack
plastics and damage pump.
For parts or assistance, call Flotec Customer Service at
Plug Switch into
115V, 3-Prong,
Grounded Outlet
2" Check Valve
Mount Horizontally!
Direction
of Flow
2" Discharge
Pipe
Float Switch must
Swing Through
Its Entire Arc
Not
to
Drill 3/16" Vent
Hole Here
Scale
Install the Pump on a
Hard, Level Surface
6164 0310
Will Handle a Flow Rate of:
12 GPM (45 LPM)
21 GPM (79 LPM)
30 GPM (113 LPM)
48 GPM (181 LPM)
3. To reduce motor noise and vibrations, a short length
of rubber hose can be connected into discharge line
near pump using suitable clamps.
4. If the pump discharge line is exposed to outside
subfreezing atmosphere, then the portion of line
exposed must be installed so any water remaining
in pipe will drain to outfall by gravity. Failure to do
this can cause water trapped in discharge to freeze
which could result in damage to pump.
5. Install a 2" check valve in the horizontal portion of
the discharge pipe. Make certain, the flow indicating
arrow, points away from the pump. This check valve
will keep the water from either running back into the
basin or into the area being pumped out when the
pump is not running. Check valve should be a free
flow valve that will easily pass solids.
NOTICE For best performance of check valve when
handling solids, do not install it with discharge angled
more than 45° above the horizontal. Do not install check
valve in a vertical position as solids may settle in valve
and prevent opening on startup.
6. Drill a 3/16" (4.7mm) hole in discharge pipe
about 1"-2" (2.5 - 5.1cm) above pump discharge
connection (but below check valve) to prevent
airlocking the pump.
7. Insert the float switch piggy-back plug into a
properly grounded outlet and the pump plug into the
piggy-back plug.
8. Check the installation by observing the pump
operation through one complete cycle. Make sure that
no parts of the assembly interfere with the float switch.
Risk of flooding. Can cause personal
injury and/or property damage. Failure to make this
operational check may lead to improper operation,
premature failure, and flooding.
ELECTRICAL
Risk of electric shock. Can shock, burn or
kill. When installing, operating, or servicing this pump,
follow safety instructions listed below.
1. DO NOT splice the electrical power cord.
2. DO NOT allow electrical cord plug to be submerged.
3. DO NOT use extension cords. They are a fire hazard
and can reduce voltage sufficiently to prevent
pumping and/or damage motor.
4. DO NOT handle or service pump while it is connected
to power supply.
5. DO NOT remove grounding prong from plug or
modify plug.To protect against electrical shock, the
power cord is a three-wire conductor and includes a
3-prong grounded plug. Plug pump into a 3-wire,
grounded, grounding-type receptacle. Connect pump
according to electrical codes that apply.
800-365-6832
3