SELECTION OF INSTALLATION

Installation of Outdoor Unit

• Before installation, check strength and horizontality of
the base so that abnormal sound does not generate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
Drain hole
Knockout hole
Set the out margin of the anchor bolt to 15mm or less.
• In case of drainning through the drain hose, attach
the following drain nipple and the waterproof rubber
cap, and use the drain hose (Inner diam.: 16mm) sold
on the market. And also seal the screws securely with
silicone material, etc. so that water does not drop
down. Some conditions may cause dewing or drip-
ping of water.
Drain nipple
Waterproof rubber cap
• When there is a possibility of freezing of drain at the
cold district or a snowfall area, be careful for drainage
ability of drain. The drainage ability increases when a
knockout hole on the base plate is opened. (Open the
knockout hole to outside using a screwdriver, etc.)
600
150
430
Drain nipple mounting hole
15 or less
Waterproof rubber cap
Knockout hole
Open
Drain nipple
Optional Installation Parts
(Local Procure)
Parts name
Refrigerant piping
A
Liquid side : Ø9.5 mm
Gas side
: Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes

Refrigerant Piping Connection

CAUTION
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak at connected points.
<Piping connection>
Liquid side
Outer diameter Thickness Outer diameter Thickness
Ø9.5
0.8
For Reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.
5
Q'ty
Each one
1
Each one
Gas side
Ø15.9
1.0