Example of allowable installation calculation ("25" version) in that the sum of the head
losses of the single fittings is less than 7,00 mm H
7 m horizontal pipe ø 80 x 0,20
7 m horizontal pipe ø 80 x 0,30
n° 2 90° elbows ø 80 x 0,30
n° 2 90° elbows ø 80 x 0,40
N° 1 terminal ø 80
Total head loss
With this total head loss, remove the ø 38 baffle from the intake pipe.
KEY
1 Sponge-rubber gasket ø 125/95
2 Fixing screw
3 Air-smokes flow splitting unit
with take-off points
4 Sectores diaphragm ø 38
120
KEY
1 Air-smokes flow splitting unit
with take-off points code 8093000
2a 90° elbow MF code 8077404
2b Isolated 90° elbow MF code 8077408
3a Extension L. 1000 code 8077303
3b Isolated extension L. 1000 code 8077306
4 Outlet terminal code 8089501
5 Int.-est. ring lit code 8091500
6 Intake terminal code 8089500
7 45° elbow MF code 8077406
8 Condensation outlet L. 135 code 8092800
9 Locking junction (n. 5) code 8092700
110
O:
2
Inlet
Outlet
1,40
2, 1 0
0,60
0,80
0, 1 0
0,30
2, 1 0
+
3,20
2.8. 1
Separate pipe accessories
Kit code 8093000 is supplied for this pur-
pose (fig. 13). The sectored diaphragm is to
be used according to the maximum head
"25" version
Sectores diaphragm
to remove
1
2
4
6
Remove diaphragm
"25 BF"version B22 type
Sectores diaphragm
to remove
1
2
3
4
5
6
Remove diaphragm
Fig. 13
loss allowed in both pipes, as given in fig.
13/a. The complete range of accessories
necessary for satisfying all installation requi-
rements is reported in fig. 14.
2.8.2
The roof outlet terminal L. 1240 cannot be
shortened and when positioning the tile, the
minimum distance from the discharge head
=
5,3 mm H
O
2
terminal must not be less than 700 mm
(fig. 15). The accessories to be used for this
type of installation and some of the connec-
ting systems that may be adopted are illu-
strated in fig. 16.
There is the possibility of doubling the air-
intake and smoke-outlet pipes and then brin-
ging them back together again so as to
obtain a concentric discharge by using the
doubler fitting (7 fig. 16).
"30" version
Sectores diaphragm
Total head loss
mm H
O
Pa
2
0 ÷ 2
0 ÷ 19,6
2 ÷ 3
19,6 ÷ 29,4
3 ÷ 4
29,4 ÷ 39,2
4 ÷ 5
39,2 ÷ 49,0
5 ÷ 7
49,0 ÷ 68,6
Remove diaphragm
Total head loss
mm H
O
Pa
2
0 ÷ 1
0 ÷ 9,8
1 ÷ 2
9,8 ÷ 19,6
2 ÷ 4
19,6 ÷ 39,2
4 ÷ 5
39,2 ÷ 49,0
5 ÷ 6
49,0 ÷ 58,8
6 ÷ 7
58,8 ÷ 68,6
7 ÷ 8
68,6 ÷ 78,4
Separate-pipes
roof outlet
Total head loss
to remove
mm H
O
Pa
2
1
0 ÷ 2
0 ÷ 19,6
2
2 ÷ 3
19,6 ÷ 29,4
3
3 ÷ 4
29,4 ÷ 39,2
4
4 ÷ 5
39,2 ÷ 49,0
5
5 ÷ 6
49,0 ÷ 58,8
6
6 ÷ 7
58,8 ÷ 68,6
7 ÷ 11 68,6 ÷ 107,8
SECTOR OF DIAPHRAGM
Fig. 13/a
Fig. 14