Technical characteristics

UPS power
Nominal input voltage
Input frequency
Voltage/frequency of battery backup outlets
8 in battery mode
Total output current for the 8 outlets
Output current of battery backup outlets 8
Leakage current
Input protection
Transfer time
Telephone surge protection
Sealed lead-acid battery
Automatic battery test
Average battery life
Operating temperature
Storage temperature
Operating relative humidity
Operating elevation
Safety standards
Electromagnetic compatibility standards
Warranty
(*) Warning: This is a class A-UPS product. In a domestic environment, this product may cause radio interference, in which
case, the user may be required to take additional measures.
Performances tested according to IEC 61643-1 (class 3) standard for 8/20 µs surge wave
AC input source protection
Uoc
Up
In
Imax
Dielectric isolation
AC Ground
AC / TEL
Tel / Ground
Temporary overvoltage (TOV)
Uc
Ut
TOV
Energy dissipation
40
Protection
Station 650
650 VA / 400 W
184 V - 264 V, adjustable to 161 V - 284 V
50/60 Hz (46 - 70 Hz working range)
220 V/ 230 V / 240V ± 7% (50/60 Hz ± 1 Hz)
with pseudosinusoidal wave
10 A max
2.8 A max
0.5 mA
10 A resettable circuit breaker
5 ms typical
Tel, ISDN, ADSL, Ethernet
12 V, 7 Ah
Once a week
4 years typical, depending on number of discharge
cycles and temperature
0 to 35°C
-25°C to +55°C
0 to 85%
0 to 3000 m
IEC 60950-1, IEC 62040-1-1, CE certified
IEC 62040-2 *
2 years
Protection
Station 800
800VA / 500 W
3.5 A max
12 V, 9 Ah
6 kV
1.7 kV
2.8 kA
8 kA
1500 Vac, 50 Hz
3000 Vac, 50 Hz
1000 Vac, 50 Hz
250 Vac
400 Vac
1450 Vac
525 Joules
MAU-00075 AB

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Protection station 800

Tabla de contenido