Descargar Imprimir esta página

Set Up/Installation - Jøtul I 18 Instrucciones Para Instalación

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
4.3 Air supply (fig. 2)
Air should be allowed to flow between the insert and the
brickwork, and it is very important that there is a free air supply
to the draft catchers on top of and under the insert.
The required air vent sizes for Jøtul I 18 (for air circulation) are:
Base: Minimum of 750 cm
Top:
Minimum of 1000 cm
This is a safety measure to prevent a build up of heat in the
surround, and also to ensure sufficient heat emission into the
room.
If the house is badly ventilated, the room must be equipped with
extra fresh air circulation, for example by means of separate
air channels or a separate channel directly to the top of the
fireplace.
The fresh air channel should be as straight as possible. Channels
in the stove must be made of fire-proof materials.
4.4 Ceiling
Jøtul I 18 should have a min. 500 mm distance from warm air
opening in the hood's top to a ceiling of c0mbustible material.
4.5 Chimney
The fireplace can be connected to a chimney and flue
pipe approved for solid fuel fired fireplaces with flue gas
temperatures specified in «2.0 Technical data».
The chimney's cross-section must be at least as big as the
flue pipe's cross-section. See «2.0 Technical data» when
calculating the correct chimney cross-section.
The fireplace must be connected to a separate chimney.
Contact your local building authorities regarding restrictions
and installation requirements
Connection to the chimney must be carried out in accordance
with the installation instructions from the supplier of the
chimney.
Before making a hole in the chimney the fireplace should be
test-mounted in order to correctly mark the position of the
fireplace and the hole in the chimney. See fig. 1 for minimum
dimensions.
Ensure that the flue pipe is inclined all the way up to the
chimney.
Use a flue pipe bend with a sweeping hatch that allows it to
be swept.
Be aware of the fact that connections must have a certain
flexibility in order to prevent movement in the installation
leading to cracks.
N.B! A correct and sealed connection is very important for the
proper functioning of the product.
Warning! Weight from the fireplace must not be transferred to the
chimney. The fireplace must not interfere with the ability of the
chimney to move and it must not be fastened to the chimney.
Note: A guide is published by the British Flue and Chimney
Manufacturers' Association which contains general information
on chimneys and flues.
Recommended chimney draught: See section «2.0 Technical
data». If the draught is too strong you can install and operate a
flue damper to control the draught.
2
free ventilation.
2
free ventilation.
In case of chimney fire
Close all hatches and vents.
Keep the firebox door closed.
Check the loft and cellar for smoke.
Call the fire service.
Before use after a fire an expert must check the fireplace in
order to ensure that it is fully functional.
4.6 Preparation/installation
Make sure that the fireplace insert is free of damage before
commencing with the installation.
Attaching the legs (fig. 5)
1. Unpack the insert.
2. Take out all the loose parts, such as the baffle plate, burn
plates and bottom plate.
3. Place the wooden pallet and the cardboard packaging on the
floor and lay the fireplace carefully down on its back.
4. Fit the three legs (5D) using 3 hex. head screws M8x35 mm
with nuts and washers.
5. Fit the adjustable extension pieces to the legs so that the ash
container (fig. 10A) is lifted at least 100 mm above the floor.
Fix the extension pieces to the legs with hex. head screws
M6 x 25 mm, and nuts.
6. For fine height adjustment, screw and M10 x 35 mm hex. screw
into the end of each adjustable extension piece.
Assembly of the heat shield (fig. 5)
Unscrew the bolt (fig. 5B) in the centre of the bottom plate until
the crossbar (fig. 5A) comes loose. Position the heat shield (fig.
5C) on the bolt (fig. 5B) from underneath with the countersunk
facing downwards and the notch facing the leg. Secure the heat
shield to the bolt with a M6 nut.
1. Place a seating washer under each bolt to protect the floor.
2. Lift the insert up.

4.7 Set up/installation

The product is heavy! Make sure you have assistance when
erecting and installing the fireplace.
Assembly of the smoke bell (fig. 6 - 7)
1. The smoke bell (fig. 6A) can be fitted in any position towards
the chimney.
2. Fit the smoke outlet (fig. 7A) onto the smoke bell, vertically
or horizontally, depending on chimney orientation. Fasten
with two screws (fig. 7B).
3. Apply sealing cement in the smoke bell bedding on top of
the insert.
4. Place the smoke bell in correct position towards the chimney
hole. If a combustion air duct (fig. 6C) is to be fitted, do so
before fastening the smoke bell.
Assembly of the heat shield for the smoke
bell (fig. 8)
1. Mount the heat shield for the smoke bell by connecting it.
2. Place the heat shield around the smoke bell with the opening
underneath the smoke outlet (fig. 8A).
ENGLISH
13

Publicidad

Capítulos

loading