6.
Electrical work
Fig. 6=7
4) Assigning
a remote controller
to each unit (Fig. 6-7)
Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a remote controller
is assigned
to the same pair No.
5) Wireless
remote controller
pair number setting
operation
Press the SET button with something
sharp at the end.
Start this operation from the status of remote controller
display turned off.
blinks and Model No. is lighted.
Press the _
button twice continuously.
Pair No. "0" blinks.
®
Press the temp _
_'_,_button to set the pair number you want to set.
_') Press the SET button with something
sharp at the end.
Set pair number is lighted for three seconds then turned off.
@ Pair No. of wireless
remote controller
Indoor PC board
0
Factory setting
1
Cut J41
2
Cut J42
3-9
Cut J41, J42
-@
<_ Mode number
(I[) Setting number
_ Refrigerant
address
@) Unit number
©
©
\
u u
_ _
/
_ _
LU _
__
C!:-I
.]--
,q,q'7-I12
_-
I
L_I_
II_
I
uu
LI_ i
__
6.3. Function
settings
6.3.1
Function
setting
on the
unit
(Selecting
the unit
functions)
1) For wired remote controller
(Fig. 6-8)
Changing
the power voltage setting
= Be sure to change the power voltage setting depending on the voltage used.
Go to the function setting mode.
Switch OFF the remote controller.
Press the @ and (_) buttons simultaneously
and hold them for at least 2
seconds. FUNCTION will start to flash.
Use the © button to set the refrigerant
address (]][) to 00.
®
Press @ and [--] will start to flash in the unit number (_)
display.
(_ Use the © button to set the unit number (IV) to 00.
(_) Press the (_ MODE button to designate
the refrigerant
address/unit
number. [--]
will flash in the mode number ( I ) display momentarily.
®
Press the (_ buttons to set the mode number ( t ) to 04.
(_ Press the (_) button and the current set setting number ( _ ) will flash.
Use the (_ button to switch the setting number
in response
to the power supply
voltage to be used.
Power supply voltage
230V
: setting number = 1
208V
: setting number-
2
®
Press the MODE button (_) and mode and the setting number ( I ) and ( _ ) will
change to being on constantly
and the contents of the setting can be confirmed.
_) Press the FILTER @ and TEST RUN _) buttons simultaneously
for at least two
seconds. The function
selection
screen will disappear
momentarily
and the air
conditioner
OFF display will appear.
,@ ®
\ _1_/-
4,-, ,1
®
\ _I_Z
\4
I /
Ji,-, ,1
l l
Fig. 6=9
2) For wireless
remote controller
(Fig. 6-9)
Changing
the power voltage setting
o Be sure to change the power voltage setting depending on the voltage used.
Go to the function select mode
Press the _
button (_ twice continuously.
(Start this operation from the status of remote controller display turned off.)
is lighted and_ "00" blinks.
Press the temp f,,v_ button @ once to set "50". Direct the wireless
remote controller
h
toward the receiver of the indoor unit and press the _
button (_).
Setting the unit number
Press the temp (\v)) ((A_button © and (_ to set the unit number"00". Direct the wireless
_J
min
remote controller toward the receiver of the indoor unit and press the _
button (_).
®
Selecting a mode
Enter 04 to change the power voltage setting using the _vj_ © and _
@ buttons.
Direct the wireless
remote controller toward the receiver of the indoor unit and press
the _
button @.
Current setting number:
1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)
(_ Selecting the setting number
© and _
@ buttons to change the power voltage setting to 01 (240 V).
Use the
Direct the wireless
remote controller
toward the sensor of the indoor unit and press
the _
button @.
(_ To select multiple functions continuously
Repeat steps ® and @ to change multiple function settings continuously.
(_ Complete function selection
Direct the wireless
remote controller
toward the sensor of the indoor unit and press
the _$_ button
®.
Note:
Whenever
changes
are made to the function
settings after installation
or main-
tenance,
be sure to record the changes
with a mark in the "Setting"
column
of
the Function
table.
6.3.2
Function
setting
on the remote controller
Refer to the indoor unit operation manual.
11