3. Installing
the indoor unit
Fig. 3-4
®
®
Fig. 3-5
Fig. 3-6
®
Fig. 3-7
_o_)
_
_....
@ Min. 140 ram,
5-1/2 inch
_) Min. 300 ram,
11-13/16
inch
© Min. 55 mm,
2-3/16 inch
@ Mount board
©
3.2.3.
Installing
the wall
mounting
fixture
II_ Since the indoor unit weighs
near 30 kg, 66 Ibs selection
of the mounting
location requires
thorough
consideration.
If the wall does not seem to be
strong enough,
reinforce
it with boards
or beams before
installation.
II_ The mounting
fixture
must be secured
at both
ends and at the centre,
if
possible. Never fix it at a single
spot or in any nonsymetrical
way.
(If possible, secure the fixture
at all the positions
marked with a bold arrow.)
(Fig. 3-4)
z_ Warning:
If possible,
secure the fixture
at all positions
indicated
with a bold arrow.
z_ Caution:
o The unit body must be mounted
horizontally.
o Fasten at the holes marked
with A as shown
by the arrows.
_) Fasten a thread to the hole.
_ The level can be easily obtained by hanging a weight from the string and aligning the string
with the mark.
3.3. When embedding
pipes into the wall (Fig. 3-5)
• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external
connection
lines etc are to be
embedded
into the wall in advance, the extruding
pipes etc, may have to be bent
and have their length modified to suit the unit.
• Use marking on the mount board as a reference when adjusting the length of the
embedded
cooling pipe.
• During construction,
give the length of the extruding
pipes etc some leeway.
(_) Mount board
(_) Reference marking for flare connection
C-C) Through hole
(_) On-site piping
3.4. Preparing the indoor unit
Rear, right and lower piping (Fig. 3-6)
1. Bind the cooling pipe and drain pipe together.
• Bind the pipes together with vinyl tape at three or more points. This will facilitate
passing the pipes through the wall.
2. Remove the corner box and knock out the knockout holes as necessary.
• Remove the corner box by pushing in a downward direction (_), while at the same
time, pressing in the upper side part of the corner box (_.
(_) Corner box
(_) Under cover
Left and left rear piping (Fig. 3-7)
1. Remove the under cover.
• Remove the under cover by sliding it towards the rear of the unit @, while at the
same time, pressing the two points marked by arrow heads (_.
2. Remove the corner box and knock out the knockout holes as necessary.
3.5. Mounting
the indoor unit
1. Affix the mounting
plate to the wall.
2. Hang the indoor unit on the two hooks positioned
on the upper part of the mount-
ing plate.
Rear, right and lower piping
(Fig. 3-8)
3. Affix the indoor unit.
4. After connecting
the pipes, put the corner box back to where it was (follow the
removal steps backwards).
(_) Square hole
(_) Hooks
®
/
Fig. 3-8
Fig. 3-9
(inch)
Left and left rear piping (Fig. 3-9)
3. Cut out a mounting
piece from the packaging
material.
4. Pull the indoor unit up towards yourself as shown in the figure below and slide the
mounting
piece in to the mounting
plate using the mounting
piece setting marks
as reference.
5. After connecting
the pipes and wiring, put the under cover back to where it was,
and remove the mounting
piece and affix the indoor
unit as shown in the left
figure.
6. Put the corner box back to where it was.
(_) Mounting piece
(_) Ceiling
© Rib
4