Descargar Imprimir esta página

Haier 1U24GS1ERA Manual De Instalación página 18

Ocultar thumbs Ver también para 1U24GS1ERA:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Installation Procedure
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC
CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
Precautions for Electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated
grip on the ends of the wires.
Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage
drop.)
Item
Model
1U24GS1ERA
1U28GS2ERA(S)
1U28HS1ERA(S)
1U36HS1ERA(S)
1U48LS1ERA(S)
1U60IS1ERA(S)
1U48LS1EAB(S)
1U48LS1ERB(S)
1U48IS1EAB(S)
1U48IS1ERB(S)
1U60IS1EAB(S)
1U60IS1ERB(S)
1U60IS2EAB(S)
1U60IS2ERB(S)
If the supply cord is damaged, it must be replaced by the manufacturer or itsservice agent or a similar qualified person.
If the fuse of control box is broken, please change it with the type of T25A/450VAC;
If the fuse of control PC board is broken, please change it with the type of T3.15A/250VAC. But for 1U24GS1ERA,
1U28GS2ERA(S),1U28HS1ERA(S),1U36HS1ERA(S),1U48LS1ERA(S),1U48LS1ERB(S),1U48IS1ERB(S),1U60IS1ERA
(S),1U60IS1ERB(S), the type is T6.3A/250VAC.
The wiring method should be in line with the local wiring standard.
The power cable and connecting cable should be self-provided.
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should not be no
less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the
diameter of the wire should be enlarged according to the local wiring standard.
A leakage breaker must be installed.
The specification of power cable
For models 1U24GS1ERA,1U28GS2ERA(S),1U28HS1ERA(S), 1U36HS1ERA(S), 1U48LS1ERA(S),1U60IS1ERA(S),
1U60IS2ERB(S) the power cable should be H05RN-F 3G 6.0mm
For models 1U48LS1EAB(S), 1U48IS1EAB(S), 1U60IS1EAB(S), 1U48LS1ERB(S), 1U48IS1ERB(S), 1U60IS1ERB(S),
1U60IS2EAB(S) the power cable should be H07RN-F 5G 4.0mm
Wiring procedure
1) Remove set screws on the side before taking off the front panel toward the direction.
2) Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped nearby the terminal block.
3) Route the wires in a proper way and penetrate the wires through the opening for electrical wiring on the side panel.
DANGER OF BODILY INJURY OR DEATH
Circuit breaker
Phase
Switch breaker
(A)
1
40
3
30
WARNING!
Overcurrent protector
rated capacity (A)
30
20
.
2
.
2
16
Power source
Earth leakage breaker
wire size
Switch
(minimum)
breaker(A)
(mm
)
2
6.0
40
4.0
30
Electrical Wiring
Leak
current(mA)
30
30

Hide quick links:

Publicidad

loading