Remote Module Led Status Indicators - Briggs & Stratton 100 Manual De Instalación

Ocultar thumbs Ver también para 100:
Tabla de contenido

Publicidad

Remote Module LED Status Indicators

Symphony II System does not communicate or manage appliances/
loads when utility power is present.
NOTICE When looking at LED's, make sure you look straight on
and not at an angle.
Low Voltage (Single and Dual) Models
A
B
C
A - Low Voltage Control Wiring Terminal Contacts
B - Priority Selector
C - Communication LED
D - Neutral Connection
E - Power/Line Connection
F - Status LED
G - Plastic Barrier
LED is for signal communication status (F).
Utility power present:
• Normal State
• Problem State (see Troubleshooting)
G
Generator power present:
• Normal State
F
• Problem State (see Troubleshooting)
E
D
-
Orange LED - No communication and appliances/loads
cannot be managed by Symphony II System
-
No LED - No power to low voltage control board; verify
correct wiring
-
Green LED - Broken LED; replace low voltage module
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
-
Green LED - Signal communication detected and
appliances/loads can be managed after 5 minute delay
-
No LED - No power to low voltage control board; verify
correct wiring
-
Orange LED - Signal communication not detected; verify
correct wiring
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires