7. Maintenance and inspection
7.1 Safety measures
Important!
i
The operator must provide any protective
clothing that may be required.
Normal maintenance work may be carried out by
operational personnel.
Important!
i
Inspections of the filling stations with ADR
approval may only be performed by
specially trained personnel.
Ask the manufacturer about these training courses.
7.2 Maintenance and inspection table
Interval
Assembly
Outside of
filling
station
As
required
Filter
insert
Container
Monthly
Piping
system
Moving
Annually
parts of the
tank
Every 2.5
Filling
years
station
Every 5
Filling
years
station
26
Action
Clean off any stuckon
dirt or petrol.
Clean coarse dirt off
the filter insert at filling
connection The filter
insert must not be
dismantled!
Visual check for damage.
Check hoses for cracks
and porosity, check
fittings for leaks (replace
defective parts).
Lubricate hinges with a
few drops of universal oil.
Inspection by experts
with:
Documentation in test
report
If test is successful:
Make entry on type
plate with waterproof
pen.
(Month/year e.g. 01/14)
Complete verification
years by manufacturer
CEMO or an authorised
partner.
Documentation in test
report
i
Important!
Always keep filling station in a
usable condition.
8. Taking out of service
8.1 Taking out of service after expiry of
the ADR approval
After expiry of the ADR approval of 5 years after
the date of manufacture. Thereafter, filling stations
may be used again in accordance with regulation
ADR 1.1.3.1 c (see point 1.2.2 of these operating
instructions).
i
Important!
As the approval number is no longer valid,
it must be made unrecognisable on the
type plate of the tank.
To this end, you can use the adhesive text label
enclosed with the tank documentation on the
KSMobil Easy. Cut out a text block in the language
of your choice (German/English/French) and stick it
over the approval number on the type plate .
1